True Reach-in and undercounter electronic controls (Carel, Danfoss ERC / ETC, LAE)

True fits Carel, Danfoss and LAE controllers. All of them show short codes for defrost, door and temperature alarms and probe faults.

What it is: Refrigerator / freezer controller. Check the maker’s name on the control (or in the True control guide) to pick the right rows.

True Reach-in and undercounter electronic controls (Carel, Danfoss ERC / ETC, LAE) error codes

CodeMeaningLikely causeWhat to do
Carel: E0 / E1 / E2Probe 1 (air) / 2 (defrost) / 3 faultProbe open, shorted or unpluggedCheck the probe (white = air, white/blue = coil).
Carel: EdDefrost ended on maximum timeHeater or coil probeCheck the defrost.
Carel: HI / LOHigh / low temperature alarmDoor, load, refrigerationClears when back in range.
Carel: dOrDoor open
Danfoss ERC: E01–E04Sensor S1–S4 faultSensorCheck the sensor.
Danfoss ERC: ConCondenser alarmDirty condenser or fanClean the condenser.
Danfoss ERC: LEARefrigerant leak alarmLeakFind and repair the leak.
Danfoss ERC: EoCControl and display not talkingCableCheck the display cable.
Danfoss ERC: non / SYnDisplay sensor not set up / display not compatibleWrong display or settingFit the right display.
Danfoss ERC: uHi / uLi (uLo)High / low supply voltageSupplyCheck the supply.
Danfoss ETC: E1 / E2Sensor 1 / 2 defectSensorCheck the sensor.
Danfoss ETC: E4 / E5 / E6Compressor / heater / set-knob (pot) faultPart failedCheck that part.
Danfoss ETC: E13Communication errorCableCheck wiring.
Danfoss ETC: Ulo / UHiLow / high supply voltageSupplyCheck the supply.
LAE: E1 / E2 / E3Probe T1 (air) / T2 (coil) / T3 (display) failureProbeCheck the probe.
LAE: hi / Lo / doHigh / low temperature / door open
LAE: thi / tLoHighest / lowest recorded air temperatureInformation
LAE: LocKeypad locked

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: True commercial refrigeration general control guide TEC_TM_001 Rev C (2025). Always check the manual for your exact model and software version.

ServiceModes is not affiliated with True or any other manufacturer. Written in our own words from the manufacturer's documentation.