Carel ir33 (refrigeration)

Panel controller for cabinets and cool rooms with up to five probes, compressor, defrost, evaporator fan, alarm and aux relays, HACCP logging and an optional real-time clock.

What it is: Refrigeration controller. Same menu logic on ir33 power, ir33 DIN, powercompact and MasterCella. The models differ in which parameters are visible.

Key combo: Frequent (F) parameters: hold PRG for 5 s. Configuration (C) parameters: hold PRG + SET for 5 s, enter the service password, press SET.

Carel ir33 (refrigeration) error codes

CodeMeaningLikely causeHow to reset
rEVirtual control probe faultThe probe (or probe mix) used for control has failedClears by itself once the probe reads again. The compressor runs on the duty setting (c4).
E0Room probe (S1) faultProbe open or shorted, wrong probe type, wiringClears by itself when the probe reads normally.
E1Defrost probe (S2) faultProbe open or shorted, wiringClears by itself. Defrost then ends on time.
E2 / E3 / E4Probe S3 / S4 / S5 faultProbe open or shorted, or a probe enabled that is not fittedClears by itself. Check the /A2–/A4 probe settings.
LOLow temperature alarmTemperature below the AL limit for longer than AdClears by itself when temperature recovers.
HIHigh temperature alarmTemperature above the AH limit for longer than AdClears by itself when temperature recovers.
AFrAntifreeze alarmTemperature below the ALF set point for longer than AdFManual reset: hold PRG + UP for 5 s once the cause is gone.
IAImmediate external alarmDigital input set as an immediate alarm has openedClears when the contact closes.
dADelayed external alarmDigital input open for longer than A7Clears when the contact closes.
Ed1 / Ed2Defrost on evaporator 1 / 2 ended on time, not temperatureDefrost heater, probe position, ice load, dt1 / dP1 too lowShown only if A8 = 1. Clears on the next defrost that ends on temperature, or by manual reset.
PdMaximum pump-down time exceededPump-down did not finish within c7Automatic or manual depending on settings.
LPLow pressure alarmLow-pressure switch input openAutomatic or manual depending on settings. Compressor stops.
AtSAuto-start in pump-downCompressor restarted itself during pump-downAutomatic or manual depending on settings.
chtHigh condenser temperature pre-alarmCondenser above Ac – dirty coil, fan faultClears by itself once the condenser cools.
CHtHigh condenser temperature alarmCondenser stayed above Ac + AE for AcdManual reset: hold PRG + UP for 5 s. Compressor stops.
dorDoor open too longDoor switch open past the set delayClears when the door closes.
EtcReal-time clock faultClock not set or clock failureSet the clock (tc parameters).
EEUnit parameter memory errorCorrupt EEPROM dataClears by itself if the error goes away. If it stays, the controller needs replacing.
EFOperating parameter memory errorCorrupt parameters, failed default set loadRe-check and re-save the parameters. Power cycle restores the previous set after a failed load.
HA / HFHACCP high-temperature / power-failure event loggedLogged temperature event or blackoutManual: in the HACCP menu, clear with UP + SET as described below.

How to enter service / parameter mode

  1. F parameters (frequent use): hold PRG for more than 5 seconds. If an alarm is active, the first press mutes the buzzer. The first F parameter appears.
  2. C parameters (configuration): hold PRG and SET together for more than 5 seconds. 00 appears (password prompt).
  3. Enter the service password with UP or DOWN, then press SET. The first C parameter appears.
  4. Press PRG at any time to jump to the category list (Pro, CtL, CMP, dEF, ALM, Fan, CnF, HcP, rtc), pick one and press SET to jump to its first parameter.

Parameter list

CodeWhat it doesRangeDefault / typical
StSet pointr1 to r20.0
rdControl differential0.1–202.0
r1 / r2Minimum / maximum set point allowedr1 −50 to r2; r2 r1 to 200−50 / 60
r3Operating mode: 0 cooling with defrost, 1 cooling only, 2 heating0–20
r4Set point change from the digital input (night mode)−20 to 203.0
/c1Probe 1 calibration offset−20 to 200.0
/A2Probe 2 use (for example 2 = evaporator, 3 = condenser)0–42
c0Compressor and fan start delay at power-up0–15 min0
c1 / c2 / c3Minimum time between starts / minimum off time / minimum on time0–15 min0
c4Duty setting (compressor run time while the control probe has failed)0–100 min0
ccContinuous cycle length0–15 h0
d0Defrost type: 0 electric/temperature, 1 hot gas/temperature, 2 electric/time, 3 hot gas/time0–40
dIInterval between defrosts0–250 h8
dt1Defrost end temperature (evaporator 1)−50 to 2004.0
dP1Maximum defrost time (evaporator 1)1–250 min30
d4 / d5Defrost at power-up / delay before that defrost0–1; 0–250 min0 / 0
d6Display during defrost: 0 dF flashing, 1 frozen reading, 2 dEF0–21
ddDrip time after defrost0–15 min2
d8Temperature alarms ignored after defrost0–15 h1
A0Alarm and fan differential0.1–202.0
A1AL / AH are relative to set point (0) or absolute (1)0–10
AL / AHLow / high temperature alarm limit−50 to 2000.0 / 0.0
AdTemperature alarm delay0–250 min120
A4 / A5Digital input 1 / 2 function0–150
A8Enable Ed1 / Ed2 (defrost ended on time) warnings0–10
Ac / AE / AcdCondenser high temperature alarm: set point / differential / delay0–200; 0.1–20; 0–250 min70.0 / 10.0 / 0
F0Evaporator fan control mode (0 by F2/F3/Fd, 1 room–evap difference, 2 evap temperature)0–20
F1Fan start temperature−50 to 2005.0
F2Fans stop when the compressor stops (1 = yes)0–11
F3Fans off during defrost (1 = off)0–11
FdFan delay after drip time0–15 min1
H1Relay 4 function (alarm, aux, light…)0–111
H2Keypad and remote control lock1–61
H4Buzzer disable (1 = off)0–10

How to change and save a setting

  1. Scroll to the parameter with UP or DOWN.
  2. Press SET to show the value.
  3. Change it with UP or DOWN.
  4. Press SET to keep it for now and go back to the code.
  5. When finished, hold PRG for more than 5 seconds to save everything to memory and exit.
  6. If you wait 60 seconds without a key, or switch off before saving, all changes are thrown away (clock settings are kept).

Other useful key presses

TaskHow
Reset manual-reset alarmsHold PRG + UP for more than 5 s once the cause has been fixed.
Restore defaults (Hdn = 0)Power off, then power on holding PRG until _Std_ shows. Only visible parameters are reset.
Set pointHold SET for 1 s, adjust with UP/DOWN, press SET to confirm.
HACCP logOpen the HACCP menu, pick HA or HF and scroll the date, time and duration of the last event.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Carel ir33 platform user manual (+030220441 rel. 2.5) and the ir33 v1.131 parameter summary. Always check the manual for your exact model and software version.

ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.