Carel easy (PJEZ)

Low-cost panel thermostat for plug-in fridges and freezers with up to three probes, compressor relay and on some models defrost, fan and aux outputs.

What it is: Refrigeration thermostat. Covers the easy, easy compact and easy split families. Parameter visibility depends on the model letter (S, X, Y, C, M).

Key combo: Hold SET for 3 s until PS shows, press SET, enter the service password with UP/DOWN, press SET.

Carel easy (PJEZ) error codes

CodeMeaningLikely causeHow to reset
E0Probe 1 (control) faultProbe open, shorted or wrong typeClears by itself when the probe reads normally. Buzzer and alarm relay on.
E1Probe 2 (defrost) faultProbe open, shorted or wrong typeClears by itself.
E2Probe 3 (condenser / product) faultProbe open, shorted or wrong typeClears by itself.
IAExternal alarm from the digital inputInput set as alarm (A4) has triggeredClears by itself after the input returns to normal.
dOrDoor open alarmDoor switch open longer than A7Clears by itself when the door closes.
LOLow temperature alarmBelow the AL limit for longer than AdClears by itself. Check AL, Ad and A0.
HIHigh temperature alarmAbove the AH limit for longer than AdClears by itself. Check AH, Ad and A0.
EEUnit parameter read errorCorrupt memoryIf it stays or keeps coming back, replace the controller.
EFOperating parameter read errorCorrupt parametersManual: re-enter and re-save the parameters.
EdLast defrost ended on time, not temperatureDefrost too short (dP), end temp (dt) too high, heater or probe problemClears after the next defrost that ends correctly. Shown only if A8 = 1.
dFDefrost running (not an alarm)Normal defrost, shown when d6 = 0Clears at the end of defrost.
chtDirty condenser pre-alarmCondenser hotter than AcClears by itself. Clean the condenser; check A4, Ac, AE, Acd.
CHtDirty condenser alarmCondenser hotter than Ac + AE for AcdManual reset after cleaning.
EtCClock faultClock in use but not setSet the time (dAY, hr, Min).
SrCMaintenance due (easy split only)Service interval reached (HMP)Set HMr = 1.

How to enter service / parameter mode

  1. Hold SET for more than 3 seconds (mute the buzzer first if an alarm is active). PS shows.
  2. Without a password you can scroll the F (frequent) parameters straight away with UP and DOWN.
  3. For C (configuration) parameters, press SET at PS, enter the service password with UP/DOWN and press SET.

Parameter list

CodeWhat it doesRangeDefault / typical
PSPassword for configuration parameters0–20022
/2Probe reading stability (filter)1–154
/4Probe shown on the display1–31
/5°C (0) or °F (1)0–10
/C1 / /C2 / /C3Probe 1 / 2 / 3 offset−50 to 500
StSet pointr1 to r24
rdControl differential0–192
r1 / r2Lowest / highest set point allowed−50 to r2; r1 to 200−50 / 90
r3Direct (cooling) or reverse (heating) operation0–20
r4Night set point change−50 to 503
c0Compressor and fan delay at power-up0–100 min0
c1 / c2 / c3Minimum time between starts / minimum off / minimum on0–100 min0
c4Compressor on time while the control probe has failed0–100 min0
cc / c6Continuous cycle length / alarm bypass after it0–15 h4 / 2
d0Defrost type0–40
dIInterval between defrosts0–199 h8
dtDefrost end temperature−50 to 1304
dPMaximum defrost time1–199 min30
d4 / d5Defrost at power-up / delay before it0–1; 0–199 min0 / 0
d6Freeze the display during defrost0–11
ddDrip time0–15 min2
d8Alarm bypass after defrost0–15 h1
A0Alarm and fan differential−20 to 202
AL / AHLow / high temperature alarm (absolute or relative)−50 to 2500 / 0
AdTemperature alarm delay0–199 min0
A4Third input function0–110
A7Digital input alarm delay0–199 min0
A8Enable the Ed warning0–10
Ac / AE / AcdDirty condenser alarm set point / differential / delay−50 to 250; 0.1–20; 0–250 min70 / 5.0 / 0
F0Evaporator fan control on (C models)0–10
F1Fan control set point−50 to 1305
F2 / F3Fans stop with compressor / fans during defrost0–11 / 1
FdFan delay after drip0–15 min1
H1AUX output use0–30
H2Keypad enable0–11
EZYQuick preset selection0–40

How to change and save a setting

  1. Scroll to the parameter with UP or DOWN. The LED for its group lights.
  2. Press SET to see the value.
  3. Change it with UP or DOWN.
  4. Press SET to keep it for now.
  5. Hold SET for more than 3 seconds to save everything and exit (the PJEZ quick sheet says 5 seconds).
  6. If no key is pressed for 60 seconds, or power is lost before saving, the changes are lost.

Other useful key presses

TaskHow
Restore defaultsPower off, then power on holding SET and DOWN. CF shows and the controller restarts on factory settings.
Quick presets (EZY)Set EZY to 1–4 to load a ready-made set of parameters for common jobs (normal or low temperature, timed or probe defrost, etc.).

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Carel easy / easy compact / easy split user manual (+030220791 rel. 3.3) and the PJEZ easy programming sheet. Always check the manual for your exact model and software version.

ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.