Two-digit panel controller (32×74 mm face) that runs the compressor, evaporator fans and defrost (electric or hot gas) from a room probe and an evaporator probe, plus one configurable digital input.

What it is: Refrigeration controller. Same keypad logic as the XR01CX, XR02CX, XR03CX and XR04CX. Defaults below are for the XR06CX.

Key combo: Hold SET + DOWN for 3 s to open the parameter list. Hold SET + DOWN again for more than 7 s to reach the hidden (full) menu.

Dixell XR06CX error codes

CodeMeaningLikely causeHow to reset
P1Room (thermostat) probe faultProbe open, shorted or badly connectedClears by itself a few seconds after the probe reads normally again. Check wiring before swapping the probe. While it shows, the compressor cycles on the Cy / Cn times.
P2Evaporator probe faultProbe open, shorted or badly connectedClears by itself once the probe reads normally. While it shows, defrost ends on time (Md) instead of temperature.
HAHigh temperature alarmRoom temperature above the AU limit for longer than AdClears by itself when temperature drops back inside the limit. Outputs are not changed.
LALow temperature alarmRoom temperature below the AL limit for longer than AdClears by itself when temperature rises back inside the limit.
EAExternal alarm from the digital input (iF = EA)Contact on the digital input changed state for longer than diClears as soon as the digital input returns to normal. Outputs are not changed.
CASerious external alarm (iF = bA)Digital input active for longer than diAll outputs switch off. Clears as soon as the digital input returns to normal.
dADoor open alarm (iF = do)Door switch open for longer than diClears when the door closes. With rd = y, control restarts even while the alarm shows.
OFKeypad lockedUP + DOWN held for 3 sHold UP + DOWN for 3 s until On shows.
ErHot Key copy failedBad or empty Hot Key, poor contactPress UP to retry the upload, or pull the key to abort.

How to enter service / parameter mode

  1. Hold SET and DOWN together for 3 seconds. The °C or °F LED starts flashing: you are in the first-level (user) list.
  2. For every parameter, release, then hold SET and DOWN again for more than 7 seconds. L2 shows, then the first parameter (Hy). This is the hidden menu with every parameter.
  3. If the first level is empty, nP shows after 3 seconds. Keep holding until L2 appears.

Parameter list

CodeWhat it doesRangeDefault / typical
SetSet pointLS to US−5.0 °C
HyDifferential (compressor cuts in at set point + Hy)0.1–25 °C / 1–45 °F2.0 °C
LS / USLowest / highest set point the user can chooseLS −55 °C to Set; US Set to 99 °C−55 °C / 99 °C
ot / oERoom / evaporator probe calibration offset−9.9 to 9.9 °C0.0
P2Evaporator probe fitted (y/n)n / yy
odDelay before outputs start at power-up0–99 min0
ACAnti-short-cycle delay (minimum compressor off time)0–50 min1
Cy / CnCompressor on / off time while the room probe has failed0–99 min15 / 30
CF / rEUnits (°C/°F) and resolution (decimal or integer)°C/°F; dE/in°C; dE
LdWhat the display shows (room probe, evap probe or set point)P1 / P2 / SPP1
dyDisplay delay0–15 min0
tdDefrost type: EL electric (compressor off) or in hot gas (compressor on)EL / inEL
dEDefrost end temperature (evaporator probe)−55 to 50 °C8.0 °C
idInterval between defrosts0–99 h6
MdMaximum defrost length (or fixed length with no evap probe)0–99 min30
ddDelay before a defrost starts0–99 min0
dFDisplay during defrost (real temp, start temp, set point or dF label)rt / it / SP / dFit
dtDrip time after defrost (0 = off)0–99 min0
dPRun a defrost at power-upy / nn
FCFan mode: cn with compressor, off in defrost; on continuous, off in defrost; cY with compressor, on in defrost; oY always oncn / on / cY / oYo-n (as printed)
FdFan delay after defrost0–99 min10
FSEvaporator temperature above which fans stay off−55 to 50 °C2.0 °C
AU / ALHigh / low temperature alarm limitsAU: ALL to 99 °C; AL: −55 °C to AU99 °C / −55 °C
AdTemperature alarm delay0–99 min15
dATemperature alarms ignored after start-up0–99 min90
iPDigital input polaritycL / oPcL
iFDigital input use: EA external alarm, bA serious alarm, do door switch, dF start defrost, Hc swap heat/coolEA / bA / do / dF / Au / Hcdo
diDigital input delay (alarm delay, or door alarm delay)0–99 min15
dCCompressor and fan status with door openno / Fn / cP / FCFC
rdKeep controlling after the door alarm delayn / yy
d1 / d2Read-only room and evaporator probe readingsread only—

How to change and save a setting

  1. Scroll with UP or DOWN to the parameter code.
  2. Press SET to show its value.
  3. Change it with UP or DOWN.
  4. Press SET to store it. The display moves on to the next parameter.
  5. To leave, press SET + UP, or wait 15 seconds without touching a key. The value is kept either way.

Other useful key presses

TaskHow
Move a parameter between levelsIn the hidden menu, press SET + DOWN on a parameter to add it to or remove it from the first level. A lit decimal point means it is in the first level.
Set point onlyHold SET for 3 s, adjust with UP/DOWN within 10 s, press SET again (or wait 10 s) to store.
Manual defrostHold DEF for more than 2 s.
Hot Key uploadController on, insert the key, press UP. uP then flashing Ed shows. Press SET, then power off and remove the key.
Hot Key downloadPower off, insert a programmed key, power on. do then flashing Ed shows; the unit restarts with the new settings after about 10 s.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Dixell XR01CX–XR06CX operating manual (2013 edition). Always check the manual for your exact model and software version.