Dixell XLR130 and XLR170

Wall or panel-mounted cool room panels (210×230 mm) that switch compressor, defrost, lights, alarm and, on the XLR170, evaporator fans. Optional real time clock for timed defrosts.

What it is: Cool room control panel. XLR130 has four relays; XLR170 has six, adding fans and hot gas defrost.

Key combo: Hold SET + DOWN for a few seconds for Pr1. Pick Pr2 and enter the service password for the full list.

Dixell XLR130 and XLR170 error codes

CodeMeaningLikely causeHow to reset
P1Thermostat probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; compressor runs on COn / COF.
P2Evaporator probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; defrost ends on time.
P3Auxiliary probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; other outputs unchanged.
HAHigh temperature alarmRoom above ALU for longer than ALdAlarm relay on. Clears when back inside the limit.
LALow temperature alarmRoom below ALL for longer than ALdAlarm relay on. Clears when back inside the limit.
EEMemory faultInternal data check failedPress any key to restart normal running. If it returns, replace the unit.
dADoor switch alarmDoor open longer than the door delayClears when the door closes.
EALExternal alarmDigital input activeClears when the input resets.
BALSerious external alarmDigital input activeClears when the input resets.
PALPressure switch alarmPressure switch tripped too oftenCheck the pressure switch circuit; see the manual for the reset.
PAnPanic alarm (person trapped in room)Panic input activated (i2F = PAn)Buzzer, alarm relay and panic light on. Check the room immediately.
rtcClock alarmReal time clock lost its timeSet the clock (models with clock only).

How to enter service / parameter mode

  1. Hold SET + DOWN for a few seconds. The first Pr1 parameter shows.
  2. Scroll to Pr2 and press SET. PAS flashes, then a flashing digit.
  3. Enter the service password one digit at a time with UP / DOWN, pressing SET after each.
  4. With the right password the full parameter list opens.

How to change and save a setting

  1. Scroll with UP or DOWN to the parameter code.
  2. Press SET to show its value.
  3. Change it with UP or DOWN.
  4. Press SET to store it and move to the next parameter.
  5. To leave, press SET + UP or wait about 15 seconds. Values are kept either way.

Other useful key presses

TaskHow
Manual defrostHold the defrost key for 3 s.
Fast freezeHold UP for 3 s.
Silence alarmPress any key. With tbA = y the alarm relay also releases.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Dixell XLR130 and XLR170 installing and operating instructions. Always check the manual for your exact model and software version.