Dixell iChill IC260 / IC261 (L and D)

One- or two-circuit controller for air or water chillers and heat pumps, with up to six compressors, pumps, condenser fans and sanitary hot water.

What it is: Chiller / heat pump controller. IC260 has 10 relays, IC261 has 14. L models have the built-in display, D models are DIN-rail with a remote keypad.

Key combo: SET + DOWN for 3 s opens Pr1; hold UP 2 s for Pr2, again for Pr3 (each asks for its level code).

Dixell iChill IC260 / IC261 (L and D) error codes

CodeMeaningLikely causeHow to reset
AP1 … AP12Probe 1 to 12 faultProbe open, shorted or not configured rightAutomatic when the probe reads. Compressors stop if it is a control or circuit probe.
AEFLEvaporator flow alarmFlow switch open (no water flow)Compressors and condenser fan off. Check pump, strainer and flow switch.
ACFLCondenser flow alarmCondenser water flow switch openCompressors off. Manual reset if set that way.
AHFL / APFLSanitary water / solar panel flow alarmFlow switch open on that loopCheck the pump and flow switch.
AtSFSupply fan overloadFan overload input trippedCompressors off. Reset the overload.
AtE1 / AtE2Evaporator pump 1 / 2 overloadPump overload input trippedCompressors stop if no other pump is available.
AtC1 / AtC2Condenser pump 1 / 2 overloadPump overload input trippedAs above.
AtAS / AtHSSanitary pump / sanitary heater overloadOverload input trippedReset the overload.
AEP1 / AEP2 / ACP1 / ACP2 / ASAn / ASUnPump maintenance dueRunning-hours limit reachedService, then reset the hour counter.
ArtC / ArtFClock error / clock faultyClock not set or failedSet the clock; replace if it returns.
Atr1 / Atr2Remote keypad 1 / 2 faultLost connection to the remote panelCheck the CAB/CJ30 cable.
ALc1 / ALc2Generic alarmDigital input set as generic alarm is activeCompressors, pumps and fans follow the alarm setting.
AEEEEPROM alarmMemory faultEverything stops. Reprogram or replace.
ACF1, ACF2 …Configuration alarmContradictory parameter settingsCorrect the configuration (unit in stand-by).
AEUnUnloading from high evaporator water temperatureWater too warmMessage only.
ALtiLow evaporator inlet temperature (air/air)Inlet air too coldCheck airflow and set points.
AEhtHigh evaporator inlet water temperatureWater above the limitCompressors stop.
AFrSupply frequency alarmMains frequency wrongCheck the supply.
ALSFPhase sequence failurePhases reversed or missingCorrect the supply wiring.
b(n)HP / b(n)LPHigh / low pressure switch, circuit (n)Pressure switch open. (n) is the circuit number, 1 or 2.Compressors of that circuit stop.
b(n)AC / b(n)AHAnti-freeze in chiller / heat pump mode, circuit (n)Water too coldCompressors of that circuit stop.
b(n)hP / b(n)lPHigh / low condensing pressure or temperature, circuit (n)From transducer or NTCCompressors of that circuit stop.
b(n)tFCondenser fan overload, circuit (n)Fan overload trippedCompressors of that circuit stop.
b(n)PH / b(n)PLPump-down alarm at stop / at start-up, circuit (n)Pump-down did not finish in timeCompressors of that circuit stop.
b(n)dFBad defrost, circuit (n)Defrost ended on time, not temperatureCheck the defrost probe and setup.
b(n)CuUnloading, circuit (n)High condenser or low evaporator temperature/pressureCapacity reduced automatically.
b(n)dsCircuit (n) disabled from keypadSwitched off by the userRe-enable in the menu.
C(n)HPCompressor (n) high pressure switchPressure switch on that compressor open. (n) = 1 to 6That compressor stops.
C(n)oPCompressor (n) oil pressure / oil level switchOil switch openThat compressor stops.
C(n)trCompressor (n) overloadThermal protection trippedReset with COtr in the function menu.
C(n)dtCompressor (n) high discharge temperatureDischarge too hotThat compressor stops.
C(n)PdCompressor (n) oil differentialOil differential switch openThat compressor stops.
C(n)dSCompressor (n) disabled from keypadSwitched off by the userRe-enable in the menu.
C(n)MnCompressor (n) maintenance dueRunning-hours limit reachedService, then reset the counter.

How to enter service / parameter mode

  1. Function menu (alarm list, compressor overload reset, alarm log, Hot Key upload): press the M key once.
  2. In the menu pick ALrM: the bottom display shows each alarm code. Scroll with up/down; press SET on one to reset it if its cause has gone.
  3. Parameters: press SET + DOWN together for 3 s for Pr1. From Pr1 hold UP 2 s for Pr2 and again for Pr3. Each level asks for its own access code (see the manual; the codes can be changed).

How to change and save a setting

  1. Scroll to the parameter family and parameter with up/down, press SET to edit.
  2. Change with up/down and press SET to store.
  3. Configuration (CF) parameters can only be changed with the unit in stand-by, not running in chiller or heat pump.

Other useful key presses

TaskHow
Reset compressor overloadFunction menu → COtr
Read / clear alarm logFunction menu → ALOG
Copy parameters to Hot KeyFunction menu → UPL

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Dixell iChill IC260/261 L/D quick reference guide (FW 1.9, 2016). Always check the manual for your exact model and software version.