Dixell XW264K and XW60VS

Cool room controllers with alarm codes spelled out (EAL, bAL, PAL) and a password on the full parameter list. XW264K has six relays and two defrost probes; XW60VS has three relays.

What it is: Cool room controller with password-protected Pr2. Covers XW264K (two evaporators, remote T620/V620 keypad) and XW60VS (100×64 mm panel unit).

Key combo: Hold SET + DOWN for a few seconds for Pr1. Pick Pr2 and enter the service password for the full list.

Dixell XW264K and XW60VS error codes

CodeMeaningLikely causeHow to reset
P1Thermostat probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; compressor cycles on the COn / COF times.
P2Evaporator probe fault (XW60VS) / first evaporator probeProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; defrost ends on time.
P3Third probe fault (second evaporator on XW264K, display probe on XW60VS)Probe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; other outputs unchanged.
HAHigh temperature alarmRoom above ALU for longer than ALdAlarm relay on. Clears when back inside the limit.
LALow temperature alarmRoom below ALL for longer than ALdAlarm relay on. Clears when back inside the limit.
EEMemory faultInternal data check failedPress any key to reset. If it returns, replace the controller.
dADoor alarm (XW60VS) / defrost time-out (XW264K)XW60VS: door open too long. XW264K: defrost ended on time, not temperatureXW60VS: clears when the door shuts. XW264K: check defrost heaters and probe.
EALExternal alarmDigital input activeAlarm relay on. Clears when the input resets.
bALSerious external alarmDigital input activeAll other outputs off. Clears when the input resets.
PALPressure switch alarmPressure switch tripped too often within didAll other outputs off. Power off and on to reset.

How to enter service / parameter mode

  1. Hold SET + DOWN for a few seconds. The first Pr1 parameter shows.
  2. Scroll to Pr2 and press SET. PAS flashes, then 0 - - with the first digit flashing.
  3. Enter the service password one digit at a time with UP / DOWN, pressing SET after each digit.
  4. With the right password the full parameter list opens.

Parameter list

CodeWhat it doesRangeDefault / typical
SetSet point (target temperature)LS to US−5.0 °C
HyDifferential: compressor cuts back in at set point + Hy0.1–25.5 °C2.0 °C
LSLowest set point a user can choose−50 °C to set point−30.0 °C
USHighest set point a user can chooseSet point to 110 °CXW264K 20 °C
ACMinimum off time between compressor stop and restart0–30 min1 min
COnCompressor run time per cycle when the room probe has failed0–255 min15 min
COFCompressor stop time per cycle when the room probe has failed0–255 min30 min
tdFDefrost typerE, rT, inrE
dtEEvaporator temperature that ends defrost−50 to 110 °C8 °C
IdFTime between defrost starts1–120 h6 h
MdFLongest a defrost can run (or fixed length with no evaporator probe)0–255 min30 min
dFdWhat the display shows during defrostrt, it, SEt, dEF, dEGit
FnCEvaporator fan mode (with compressor or always on; on or off in defrost)C-n, C-Y, O-n, O-YO-n
FndFan delay after defrost0–255 min10 min
FStFans stop above this evaporator temperature−50 to 110 °C2 °C
ALCAlarm limits as absolute values (Ab) or relative to set point (rE)rE / AbXW264K rE; XW60VS Ab
ALUHigh temperature alarm limit−50 to 110 °CXW264K 10 (rel.); XW60VS 110
ALLLow temperature alarm limit−50 to 110 °CXW264K 10 (rel.); XW60VS −40.0
ALdDelay before a temperature alarm shows0–255 min15 min
dAOTemperature alarm hold-off after power-up (hours.tens of minutes)0 to 23 h 50 min1.3
OtRoom probe offset (calibration)−12 to 12 °C0
i2FWhat the second digital input doesEAL, bAL, PAL, dor…XW264K EAL; XW60VS dor

How to change and save a setting

  1. Scroll with UP or DOWN to the parameter code.
  2. Press SET to show its value.
  3. Change it with UP or DOWN.
  4. Press SET to store it and move to the next parameter.
  5. To leave, press SET + UP or wait about 15 seconds. Values are kept either way.

Other useful key presses

TaskHow
Manual defrostHold the defrost key for 3 s.
Fast freezeHold UP for 3 s.
Move a parameter into Pr1In Pr2, press SET + DOWN on it. A lit decimal point means it is in Pr1.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Dixell XW264K and XW60VS installing and operating instructions. Always check the manual for your exact model and software version.