Dixell XW264K and XW60VS
Cool room controllers with alarm codes spelled out (EAL, bAL, PAL) and a password on the full parameter list. XW264K has six relays and two defrost probes; XW60VS has three relays.
What it is: Cool room controller with password-protected Pr2. Covers XW264K (two evaporators, remote T620/V620 keypad) and XW60VS (100×64 mm panel unit).
Key combo: Hold SET + DOWN for a few seconds for Pr1. Pick Pr2 and enter the service password for the full list.
Dixell XW264K and XW60VS error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| P1 | Thermostat probe fault | Probe open, shorted, unplugged or wrong type (PbC) | Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; compressor cycles on the COn / COF times. |
| P2 | Evaporator probe fault (XW60VS) / first evaporator probe | Probe open, shorted, unplugged or wrong type (PbC) | Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; defrost ends on time. |
| P3 | Third probe fault (second evaporator on XW264K, display probe on XW60VS) | Probe open, shorted, unplugged or wrong type (PbC) | Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Alarm relay on; other outputs unchanged. |
| HA | High temperature alarm | Room above ALU for longer than ALd | Alarm relay on. Clears when back inside the limit. |
| LA | Low temperature alarm | Room below ALL for longer than ALd | Alarm relay on. Clears when back inside the limit. |
| EE | Memory fault | Internal data check failed | Press any key to reset. If it returns, replace the controller. |
| dA | Door alarm (XW60VS) / defrost time-out (XW264K) | XW60VS: door open too long. XW264K: defrost ended on time, not temperature | XW60VS: clears when the door shuts. XW264K: check defrost heaters and probe. |
| EAL | External alarm | Digital input active | Alarm relay on. Clears when the input resets. |
| bAL | Serious external alarm | Digital input active | All other outputs off. Clears when the input resets. |
| PAL | Pressure switch alarm | Pressure switch tripped too often within did | All other outputs off. Power off and on to reset. |
How to enter service / parameter mode
- Hold SET + DOWN for a few seconds. The first Pr1 parameter shows.
- Scroll to Pr2 and press SET. PAS flashes, then 0 - - with the first digit flashing.
- Enter the service password one digit at a time with UP / DOWN, pressing SET after each digit.
- With the right password the full parameter list opens.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| Set | Set point (target temperature) | LS to US | −5.0 °C |
| Hy | Differential: compressor cuts back in at set point + Hy | 0.1–25.5 °C | 2.0 °C |
| LS | Lowest set point a user can choose | −50 °C to set point | −30.0 °C |
| US | Highest set point a user can choose | Set point to 110 °C | XW264K 20 °C |
| AC | Minimum off time between compressor stop and restart | 0–30 min | 1 min |
| COn | Compressor run time per cycle when the room probe has failed | 0–255 min | 15 min |
| COF | Compressor stop time per cycle when the room probe has failed | 0–255 min | 30 min |
| tdF | Defrost type | rE, rT, in | rE |
| dtE | Evaporator temperature that ends defrost | −50 to 110 °C | 8 °C |
| IdF | Time between defrost starts | 1–120 h | 6 h |
| MdF | Longest a defrost can run (or fixed length with no evaporator probe) | 0–255 min | 30 min |
| dFd | What the display shows during defrost | rt, it, SEt, dEF, dEG | it |
| FnC | Evaporator fan mode (with compressor or always on; on or off in defrost) | C-n, C-Y, O-n, O-Y | O-n |
| Fnd | Fan delay after defrost | 0–255 min | 10 min |
| FSt | Fans stop above this evaporator temperature | −50 to 110 °C | 2 °C |
| ALC | Alarm limits as absolute values (Ab) or relative to set point (rE) | rE / Ab | XW264K rE; XW60VS Ab |
| ALU | High temperature alarm limit | −50 to 110 °C | XW264K 10 (rel.); XW60VS 110 |
| ALL | Low temperature alarm limit | −50 to 110 °C | XW264K 10 (rel.); XW60VS −40.0 |
| ALd | Delay before a temperature alarm shows | 0–255 min | 15 min |
| dAO | Temperature alarm hold-off after power-up (hours.tens of minutes) | 0 to 23 h 50 min | 1.3 |
| Ot | Room probe offset (calibration) | −12 to 12 °C | 0 |
| i2F | What the second digital input does | EAL, bAL, PAL, dor… | XW264K EAL; XW60VS dor |
How to change and save a setting
- Scroll with UP or DOWN to the parameter code.
- Press SET to show its value.
- Change it with UP or DOWN.
- Press SET to store it and move to the next parameter.
- To leave, press SET + UP or wait about 15 seconds. Values are kept either way.
Other useful key presses
| Task | How |
|---|---|
| Manual defrost | Hold the defrost key for 3 s. |
| Fast freeze | Hold UP for 3 s. |
| Move a parameter into Pr1 | In Pr2, press SET + DOWN on it. A lit decimal point means it is in Pr1. |
Notes
- tdF on these models: rE = electric heater, rT = thermostatic electric defrost, in = hot gas.
- Defaults differ between the two models where shown. Check the unit before relying on them.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Dixell XW264K and XW60VS installing and operating instructions. Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Dixell or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Dixell pages
- Dixell XR06CXRefrigeration controller
- Dixell XR10CX, XR20CX and XR30CXSingle-stage refrigeration controller
- Dixell XR35CX and XR40CXRefrigeration controller with defrost
- Dixell XR60CX family (XR60CX, XR64CX, XR70CX, XR72CX, XR75CX)Refrigeration controller with fans and defrost
- Dixell XR80CXMilk tank controller
- Dixell XW20L, XW40L, XW60L and XW60LSWing-style cool room controller
- Dixell XW60KCool room controller with remote keypad
- Dixell XLR130 and XLR170Cool room control panel
- Dixell iChill IC100CX seriesChiller and heat pump controller