Dixell XW20L, XW40L, XW60L and XW60LS
Wide-format controllers for cool rooms and cabinets, with a light key and optional real time clock. Relay count rises from XW20L (compressor, light) to XW60L (compressor, defrost, fans, light).
What it is: Wing-style cool room controller. Covers XW20L, XW40L, XW60L and XW60LS (38×185 mm wide keypad).
Key combo: Hold SET + DOWN for 3 s for the user level. Hold SET + DOWN again for over 7 s for the hidden menu (Pr2).
Dixell XW20L, XW40L, XW60L and XW60LS error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| P1 | Room (thermostat) probe fault | Probe open, shorted, unplugged or wrong type (PbC) | Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Compressor cycles on the COn / COF times meanwhile. |
| P2 | Evaporator probe fault | Probe open, shorted, unplugged or wrong type (PbC) | Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Defrost ends on time (MdF) meanwhile. |
| P3 | Third probe fault | Probe open, shorted, unplugged or wrong type (PbC) | Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Outputs carry on as normal. |
| P4 | Fourth (condenser / Hot Key socket) probe fault | Probe open, shorted, unplugged or wrong type (PbC) | Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Outputs carry on as normal. |
| HA | High temperature alarm | Room probe above ALU for longer than ALd | Clears by itself once back inside the limit. Outputs unchanged. |
| LA | Low temperature alarm | Room probe below ALL for longer than ALd | Clears by itself once back inside the limit. Outputs unchanged. |
| HA2 | Condenser high temperature | Condenser probe above AU2 (dirty condenser, fan fault) | Clears when the temperature drops. Compressor stops only if AC2 = y. |
| LA2 | Condenser low temperature | Condenser probe below AL2 | Clears when the temperature rises. Compressor stops only if bLL = y. |
| dA | Door open alarm (i1F = dor) | Door switch open longer than did | Clears when the door closes. Compressor and fans restart. |
| EA | External alarm (i1F = EAL) | Digital input active longer than did | Clears when the input goes back to normal. Outputs unchanged. |
| CA | Serious external alarm (i1F = bAL) | Digital input active | All outputs off. Clears when the input goes back to normal. |
| CA | Pressure switch alarm (i1F = PAL) | Pressure switch tripped nPS times within did | All outputs off. Power the controller off and on to reset. |
| PA | Pressure switch alarm (XW60LS only) | Pressure switch tripped nPS times within did | All outputs off. Power off and on to reset. |
| rtc | Clock has lost its time | Real time clock not set or lost after a long power cut | Set the time and date in the clock menu. Defrosts run on IdF meanwhile. |
| rtF | Clock board fault | Real time clock failed | Defrosts run on IdF meanwhile. Controller needs repair or replacement. |
How to enter service / parameter mode
- Hold SET and DOWN together for 3 seconds. The °C or °F light flashes: you are in the user level (Pr1).
- Let go, then hold SET and DOWN again for more than 7 seconds. Pr2 shows, then Hy. You are now in the hidden menu with every parameter.
- If the user level is empty, noP shows first. Keep holding until Pr2 appears.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| Set | Set point (target temperature) | LS to US | −5.0 °C |
| Hy | Differential: compressor cuts back in at set point + Hy | 0.1–25.5 °C | 2.0 °C |
| LS | Lowest set point a user can choose | −50 °C to set point | −50.0 °C |
| US | Highest set point a user can choose | Set point to 110 °C | 110 °C |
| Ot | Room probe offset (calibration) | −12 to 12 °C | 0.0 |
| P2P | Evaporator probe fitted? (n = no, defrost ends on time) | n / Y | Y |
| OE | Evaporator probe offset | −12 to 12 °C | 0.0 |
| COn | Compressor run time per cycle when the room probe has failed | 0–255 min | 15 min |
| COF | Compressor stop time per cycle when the room probe has failed | 0–255 min | 30 min |
| tdF | Defrost type | EL / in | EL |
| dtE | Evaporator temperature that ends defrost | −50 to 50 °C | 8 °C |
| IdF | Time between defrost starts | 1–120 h | 6 h |
| MdF | Longest a defrost can run (or fixed length with no evaporator probe) | 0–255 min | 30 min |
| dFd | What the display shows during defrost | rt, it, SEt, dEF | it |
| FnC | Evaporator fan mode (with compressor or always on; on or off in defrost) | C-n, o-n, C-Y, o-Y | o-n |
| Fnd | Fan delay after defrost | 0–255 min | 10 min |
| ALU | High temperature alarm limit | Set point to 110 °C | 110 °C |
| ALL | Low temperature alarm limit | −50 °C to set point | −50.0 °C |
| ALd | Delay before a temperature alarm shows | 0–255 min | 15 min |
| i1F | What the digital input does (door, external alarm, pressure switch, defrost, etc.) | EAL, bAL, PAL, dor, dEF, Htr, AUS | dor |
| i2F | What the second digital input does | EAL, bAL, PAL, dor, dEF, Htr, AUS | EAL |
| odc | What stops when the door opens | no, Fan, CPr, F_C | F-c |
| PbC | Probe type (PTC or NTC; Pt1000 on some versions) | PTC / NTC | NTC |
| onF | Whether the front key can switch the controller off | nu, oFF, ES | oFF |
How to change and save a setting
- Scroll with UP or DOWN to the parameter code.
- Press SET to show its value.
- Change it with UP or DOWN.
- Press SET to store it and move to the next parameter.
- To leave, press SET + UP or wait about 15 seconds. Values are kept either way.
Other useful key presses
| Task | How |
|---|---|
| Lock or unlock keys | Hold UP + DOWN for 3 s. PoF = locked, Pon = unlocked. |
| Lowest / highest recorded temperature | Tap DOWN (Lo) or UP (Hi). Hold SET while it shows to clear it. |
| Move a parameter between Pr2 and Pr1 | In the hidden menu press SET + DOWN on the parameter. A lit decimal point means it is in Pr1. |
| Other messages | noP = nothing in Pr1 or that probe is disabled; noA = no alarm stored. |
| Manual defrost | Hold the DEF key for about 3 s. |
| Light | Press the light key (when oA3 = Lig). |
Notes
- Defaults shown are from the XW60L manual.
- XW20L has no defrost relay or fan relay, so defrost and fan settings do not apply. XW40L has no fan relay.
- XW60LS has three relays (no light relay), up to three probes (no P4) and shows PA instead of CA for the pressure switch.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Dixell XW20L, XW40L, XW60L and XW60LS installing and operating instructions. Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Dixell or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Dixell pages
- Dixell XR06CXRefrigeration controller
- Dixell XR10CX, XR20CX and XR30CXSingle-stage refrigeration controller
- Dixell XR35CX and XR40CXRefrigeration controller with defrost
- Dixell XR60CX family (XR60CX, XR64CX, XR70CX, XR72CX, XR75CX)Refrigeration controller with fans and defrost
- Dixell XR80CXMilk tank controller
- Dixell XW60KCool room controller with remote keypad
- Dixell XW264K and XW60VSCool room controller with password-protected Pr2
- Dixell XLR130 and XLR170Cool room control panel
- Dixell iChill IC100CX seriesChiller and heat pump controller