Dixell XR80CX

32×74 mm controller for milk cooling tanks. One probe runs the compressor, and a second relay runs the agitator on timed cycles.

What it is: Milk tank controller

Key combo: Hold SET + DOWN for 3 s for the user level. Hold SET + DOWN again for over 7 s for the hidden menu (Pr2).

Dixell XR80CX error codes

CodeMeaningLikely causeHow to reset
P1Tank probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Compressor cycles on the Con / CoF times meanwhile.
HAHigh temperature alarmMilk above ALU for longer than ALdClears by itself when back inside the limit.
LALow temperature alarmMilk below ALL for longer than ALdClears by itself when back inside the limit.
dADoor / lid open alarmDoor input open longer than didClears when it closes. Compressor and agitator restart.
EAExternal alarmDigital input activeClears when the input goes back to normal.
CASerious external alarm (bAL) or pressure switch (PAL)Digital input activeAll outputs off. bAL clears when the input resets; PAL needs a power off and on.
EEMemory faultInternal memory check failedController needs service or replacement.

How to enter service / parameter mode

  1. Hold SET and DOWN together for 3 seconds. The °C or °F light flashes: you are in the user level (Pr1).
  2. Let go, then hold SET and DOWN again for more than 7 seconds. Pr2 shows, then Hy. You are now in the hidden menu with every parameter.
  3. If the user level is empty, noP shows first. Keep holding until Pr2 appears.

Parameter list

CodeWhat it doesRangeDefault / typical
HyDifferential: compressor cuts back in at set point + Hy0.1–25.5 °C2.0 °C
LSLowest set point a user can choose−50 °C to set point−30.0 °C
USHighest set point a user can chooseSet point to 110 °C20.0 °C
ACMinimum off time between compressor stop and restart0–50 min1 min
COnCompressor run time per cycle when the room probe has failed0–255 min15 min
AGCAgitator runs with the compressor (EL) or on its own timer (in)EL / inCheck on unit
iAGTime between agitation cycles1–120 minCheck on unit
AGtLength of an agitation cycle0–255 (min or s)Check on unit
APoRun an agitation cycle straight after power-upn / YCheck on unit
ALUHigh temperature alarm limitAlarm range100
ALLLow temperature alarm limitAlarm range−50.0
ALdDelay before a temperature alarm shows0–255 min15 min
i1FWhat the digital input does (door, external alarm, pressure switch, defrost, etc.)EAL, bAL, PAL, dor, AGt, AUS, Htr, FAn…EAL
PbCProbe type (PTC or NTC; Pt1000 on some versions)PTC / NTCNTC
onFWhether the front key can switch the controller offnu, oFF, ESnu

How to change and save a setting

  1. Scroll with UP or DOWN to the parameter code.
  2. Press SET to show its value.
  3. Change it with UP or DOWN.
  4. Press SET to store it and move to the next parameter.
  5. To leave, press SET + UP or wait about 15 seconds. Values are kept either way.

Other useful key presses

TaskHow
Start or stop an agitation cyclePress the AGT (UP) key.
Lock or unlock keysHold UP + DOWN for 3 s.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Dixell XR80CX installing and operating instructions. Always check the manual for your exact model and software version.