Two-line controller for small air or water chillers and heat pumps. Codes show on the lower display, alternating with the probe reading, and most alarms switch to manual reset if they repeat too often in an hour.

What it is: Chiller and heat pump controller. The original IC100CX range. The newer IC100CX EVO uses a different alarm code list and is not covered here.

Key combo: Hold SET + DOWN for a few seconds for Pr1. Pick Pr2 and enter the service password for factory parameters.

Dixell iChill IC100CX series error codes

CodeMeaningLikely causeHow to reset
P1–P4Probe 1 to 4 faultProbe faulty or disconnectedResets by itself when the reading recovers.
A01High pressure switch alarmHigh pressure input openAutomatic at first; becomes manual after the number of trips set in AL10.
A02Low pressure switch alarmLow pressure input openAutomatic at first; becomes manual after repeated trips within an hour.
A03Low supply (leaving) temperatureProbe 1 below the AR03 limit for AR05 secondsAutomatic when the temperature rises above AR03 + AR04.
A04Low air temperature leaving the evaporatorProbe 2 below AR03 for AR05 secondsAutomatic; becomes manual after Ar06 events in an hour.
A05High condensing temperature / pressureProbe 3 or 4 above AL11Automatic; becomes manual after repeated events. Check condenser and fans.
A06Low condensing temperature / pressureProbe 3 or 4 below AL14Automatic; becomes manual after repeated events.
A07Anti-freeze alarmAnti-freeze input active, or anti-freeze probe below AR03 (chiller) / AR27 (heat pump)Automatic; becomes manual after Ar06 events in an hour.
A08Evaporator water flow alarmFlow switch open (ignored for AL04 after pump start)Automatic once flow returns for AL07; manual if it stays open for AL05.
A09Compressor 1 overloadCompressor 1 thermal protection input activeManual reset once the cause is cleared.
A10Compressor 2 overloadCompressor 2 thermal protection input activeManual reset once the cause is cleared.
A11Condenser fan overloadFan thermal protection input activeManual reset once the cause is cleared.
A12Defrost ended on timeDefrost reached its maximum time (dF07)Clears on the next good defrost, or reset manually.
A13Compressor 1 service dueRun hours above CO14Reset the run-hour counter in the menu.
A14Compressor 2 service dueRun hours above CO15Reset the run-hour counter in the menu.
A15Water pump / supply fan service dueRun hours above CO16Reset the run-hour counter in the menu.
A16High evaporator inlet water temperatureInlet reading above AL24 (ignored for AL26 after compressor start)Automatic below AL24 − AL25; manual after repeated events.
A17Evaporator pump / supply fan overloadThermal protection input activeManual reset once the cause is cleared.
A18Condenser water pump overloadThermal protection input activeManual reset once the cause is cleared.
A19Condenser water flow alarmCondenser flow switch open (only if AL32 is not 0)Automatic once flow returns for AL31; manual if it stays open for AL29.
A20Condenser pump service dueRun hours above CO28Reset the run-hour counter.
rtCClock needs settingReal time clock lost its timeSet the clock, then reset the alarm.
rtFClock faultClock circuit failedReset manually; replace the controller if it returns.
EEMemory errorPossible loss of stored dataCheck all parameters, then reset. Replace the controller if it returns.
ACF1–ACF5Configuration alarmParameters contradict each other (for example heat pump set up without a reversing valve, or two inputs given the same job)Correct the configuration parameters.
AFrSupply frequency alarmMains frequency out of rangeCheck the power supply.

How to enter service / parameter mode

  1. Hold SET + DOWN for a few seconds. The upper display shows ALL, the first parameter group.
  2. Scroll the groups with UP / DOWN and press SET to open one.
  3. For factory (Pr2) parameters, find Pr2 in Pr1 and press SET. Pas shows with a flashing 0.
  4. Enter the service password with UP / DOWN and press SET to confirm.

How to change and save a setting

  1. Open Pr1 or Pr2 and select the parameter.
  2. Press SET to show its value.
  3. Change it with UP or DOWN.
  4. Press SET to store it.

Other useful key presses

TaskHow
View and reset active alarmsOpen the menu function, scroll to ALrM and press SET. rSt means the alarm can be reset now; NO means the cause is still there.
Alarm logStored in the menu; holds the last 50 alarms, oldest dropped first.
Silence the buzzerPress and release any key.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Dixell iChill IC100CX quick reference guide (rel. 1.0). Always check the manual for your exact model and software version.