Dixell XR35CX and XR40CX

Two-relay panel controllers. The XR40CX runs compressor and defrost (electric or hot gas). The XR35CX runs the compressor with off-cycle defrost plus a configurable second relay, and can have a real time clock.

What it is: Refrigeration controller with defrost. Covers XR35CX and XR40CX. Both 32×74 mm with a room and an evaporator probe.

Key combo: Hold SET + DOWN for 3 s for the user level. Hold SET + DOWN again for over 7 s for the hidden menu (Pr2).

Dixell XR35CX and XR40CX error codes

CodeMeaningLikely causeHow to reset
P1Room (thermostat) probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Compressor cycles on the COn / COF times meanwhile.
P2Evaporator probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Defrost ends on time (MdF) meanwhile.
P3Third probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Outputs carry on as normal.
P4Fourth (condenser / Hot Key socket) probe faultProbe open, shorted, unplugged or wrong type (PbC)Clears by itself a few seconds after the probe reads normally. Check wiring and PbC before replacing the probe. Outputs carry on as normal.
HAHigh temperature alarmRoom probe above ALU for longer than ALdClears by itself once back inside the limit. Outputs unchanged.
LALow temperature alarmRoom probe below ALL for longer than ALdClears by itself once back inside the limit. Outputs unchanged.
HA2Condenser high temperatureCondenser probe above AU2 (dirty condenser, fan fault)Clears when the temperature drops. Compressor stops only if AC2 = y.
LA2Condenser low temperatureCondenser probe below AL2Clears when the temperature rises. Compressor stops only if bLL = y.
dADoor open alarm (i1F = dor)Door switch open longer than didClears when the door closes. Compressor follows rrd.
EAExternal alarm (i1F = EAL)Digital input active longer than didClears when the input goes back to normal. Outputs unchanged.
CASerious external alarm (i1F = bAL)Digital input activeAll outputs off. Clears when the input goes back to normal.
CAPressure switch alarm (i1F = PAL)Pressure switch tripped nPS times within didAll outputs off. Power the controller off and on to reset.
rtcClock has lost its timeReal time clock not set or lost after a long power cutSet the time and date in the clock menu. Defrosts run on IdF meanwhile.
rtFClock board faultReal time clock failedDefrosts run on IdF meanwhile. Controller needs repair or replacement.

How to enter service / parameter mode

  1. Hold SET and DOWN together for 3 seconds. The °C or °F light flashes: you are in the user level (Pr1).
  2. Let go, then hold SET and DOWN again for more than 7 seconds. Pr2 shows, then Hy. You are now in the hidden menu with every parameter.
  3. If the user level is empty, noP shows first. Keep holding until Pr2 appears.

Parameter list

CodeWhat it doesRangeDefault / typical
SetSet point (target temperature)LS to USXR40CX −5.0 °C; XR35CX 3.0 °C
HyDifferential: compressor cuts back in at set point + Hy0.1–25.5 °C2.0 °C
LSLowest set point a user can choose−50 °C to set point−50.0 °C
USHighest set point a user can chooseSet point to 110 °C110 °C
OtRoom probe offset (calibration)−12 to 12 °C0.0
P2PEvaporator probe fitted? (n = no, defrost ends on time)n / YY
OEEvaporator probe offset−12 to 12 °C0.0
ACMinimum off time between compressor stop and restart0–50 min1 min
COnCompressor run time per cycle when the room probe has failed0–255 min15 min
COFCompressor stop time per cycle when the room probe has failed0–255 min30 min
tdFDefrost typeEL (electric) / in (hot gas)EL
dtEEvaporator temperature that ends defrost−50 to 50 °C8 °C
IdFTime between defrost starts1–120 hXR40CX 6 h; XR35CX 8 h
MdFLongest a defrost can run (or fixed length with no evaporator probe)0–255 minXR40CX 30 min; XR35CX 20 min
dFdWhat the display shows during defrostrt, it, SEt, dEFit
dAdLongest the display stays frozen after defrost0–255 min30 min
ALUHigh temperature alarm limitSet point to 110 °C110 °C
ALLLow temperature alarm limit−50 °C to set point−50.0 °C
ALdDelay before a temperature alarm shows0–255 min15 min
didDelay before a digital input alarm shows0–255 minCheck on unit
odcWhat stops when the door opensno, Fan, CPr, F_CCheck on unit
PbCProbe type (PTC or NTC; Pt1000 on some versions)PTC / NTC (XR35CX: Pt1000 / NTC)NTC

How to change and save a setting

  1. Scroll with UP or DOWN to the parameter code.
  2. Press SET to show its value.
  3. Change it with UP or DOWN.
  4. Press SET to store it and move to the next parameter.
  5. To leave, press SET + UP or wait about 15 seconds. Values are kept either way.

Other useful key presses

TaskHow
Lock or unlock keysHold UP + DOWN for 3 s. PoF = locked, Pon = unlocked.
Lowest / highest recorded temperatureTap DOWN (Lo) or UP (Hi). Hold SET while it shows to clear it.
Move a parameter between Pr2 and Pr1In the hidden menu press SET + DOWN on the parameter. A lit decimal point means it is in Pr1.
Other messagesnoP = nothing in Pr1 or that probe is disabled; noA = no alarm stored.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Dixell XR35CX and XR40CX installing and operating instructions. Always check the manual for your exact model and software version.