Carel ir33 Universal

General-purpose controller for temperature, humidity, pressure and similar loops, with two set points, up to four outputs and P, PI or PID control.

What it is: Universal controller (heating, cooling, PID). Two-probe, multi-output universal version of the ir33.

Carel ir33 Universal error codes

CodeMeaningLikely causeHow to reset
E01Probe B1 faultProbe open or shorted, wrong probe type (c13)Clears by itself.
E02Probe B2 faultProbe open or shorted, wrong probe typeClears by itself.
E03Digital input openInput set as external alarm has opened (immediate, delayed or manual-reset type)Automatic, or manual for the manual-reset types.
E04High temperature alarm, probe 1Above P26Clears by itself.
E05Low temperature alarm, probe 1Below P25Clears by itself.
E06Real-time clock faultClock lost or not setAutomatic or manual. Set the clock (tc).
E07Unit parameter memory errorEEPROM faultClears by itself if it goes away.
E08Operating parameter memory errorEEPROM faultClears by itself if it goes away.
E09–E15PID auto-tuning errorsAuto-tune could not finish, or calculated gains/times are invalid, or conditions were not right to startManual reset. Check the loop and retry auto-tune (c64).
E16High temperature alarm, probe 2Above P31Clears by itself.
E17Low temperature alarm, probe 2Below P30Clears by itself.
E18Digital input open (signal only)Input set to signal onlyClears by itself.
E19Digital input open, circuit 2Input set as circuit 2 alarmAutomatic or manual depending on setting.

Parameter list

CodeWhat it doesRangeDefault / typical
St1 / St2Set point 1 / 2c21–c22 / c23–c2420 / 40
c0Operating mode: 1 all direct (cooling), 2 all reverse (heating), 3 half and half, 4 PWM, 5 alarm, 6–9 mode change or two set points from the digital input0–92
P1 / P2Differential 1 / 20.1–99.92.0 / 2.0
P3Dead zone differential0–99.92.0
c4Compensation coefficient (modes 1 and 2)−2 to 20.5
c5Control type: 0 P, 1 PI0–10
c6Delay between stage starts0–255 s5
c7Minimum time between starts of the same output0–15 min0
c8 / c9Minimum off / on time for each output0–15 min0
c10Output state with a probe fault (0 all off, 1 all on, 2 cool on heat off, 3 cool off heat on)0–30
c11Output rotation0–70
c13Probe type (0 NTC, 1 NTC high temp, 2 PTC, 3 Pt1000 … 7–10 thermocouples, 11–16 voltage/current)0–160
P14 / P15Probe 1 / 2 calibration−99 to 99.90
c18°C (0) or °F (1)0–10
P25 / P26Probe 1 low / high alarm threshold−199 to 800−50 / 150
P27 / P28Probe 1 alarm differential / delay0–99.9; 0–250 min2 / 120
P29Probe 1 alarm type (0 relative, 1 absolute)0–11
c29 / c30Digital input 1 / 2 function0–120
c50Keypad / remote lock (0 keypad off, 1 all on, 2 all off)0–21
c64PID auto-tuning (1 = on)0–10

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Carel ir33 Universal parameter summary (+AU00IR33U rev 2.0). Always check the manual for your exact model and software version.

ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.