Carel EVD evolution
Stepper-valve driver that controls superheat on its own or under a pCO. Alarms show as a flashing ALARM on the display board, or as LED patterns on the LED board.
What it is: Electronic expansion valve driver. Single and twin drivers, LED board or display board.
Key combo: Press PRG, then enter the service password (or the manufacturer password for every category).
Carel EVD evolution error codes
| Alarm | What it means | What to check |
|---|---|---|
| Probe S1 / S2 / S3 / S4 | Probe faulty or reading outside its alarm range | Probe wiring, probe type and its alarm min / max settings |
| LowSH | Low superheat protection active | Low superheat threshold and timeout |
| LOP | Low evaporating temperature protection active | LOP threshold and timeout |
| MOP | High evaporating temperature protection active | MOP threshold and timeout |
| High Tcond | High condensing temperature protection active | Condenser, fans and the threshold |
| Low suction temperature | Suction temperature below threshold for the timeout | Threshold and timeout |
| EEPROM damaged | Unit or operating parameter memory damaged | Control stops completely. Replace the driver or contact service |
| EEV motor error | Valve motor fault or not connected | Valve cable and motor; switch the driver off and on |
| LAN error | Network communication problem | Network address and cabling; pCO powered and running |
| Display connection error | No communication between display and driver | Display and connectors |
| Adaptive control ineffective | Auto-tuning failed | Main control setting |
| Battery discharged | Backup battery flat, faulty or disconnected | Replace the battery if it persists after recharge time |
| Wrong power supply mode | DC supply with the AC power mode set | Power supply mode parameter and supply |
| Pressure / temperature difference | Difference between paired probes too large | Probe wiring and probe alarm settings |
How to enter service / parameter mode
- Press Esc until the standard screen shows.
- Press PRG. A password screen appears.
- Press ENTER and key in the service password digit by digit, starting from the right, confirming each with ENTER.
- The first editable parameter shows. Use UP / DOWN to move through the list.
How to change and save a setting
- Select the parameter with UP / DOWN.
- Press ENTER to go to its value.
- Change it with UP / DOWN and press ENTER to confirm.
- Press Esc to leave programming.
Other useful key presses
| Task | How |
|---|---|
| See the alarm queue | Press Help (or PRG while in alarm), then scroll with UP / DOWN. |
Notes
- All EVD evolution alarms reset by themselves once the cause clears, except where the table says to replace a part or change a setting.
- Control alarms can be switched off by setting their timeout to 0. Check this if an expected alarm never appears.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Carel EVD evolution user manual (+0300005EN rel. 3.4). Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Carel pages
- Carel ir33 (refrigeration)Refrigeration controller
- Carel easy (PJEZ)Refrigeration thermostat
- Carel ir33 UniversalUniversal controller (heating, cooling, PID)
- Carel MPXPRODisplay case and cold room controller
- Carel MPXoneDisplay case and cold room controller
- Carel UltraCellaCold room controller
- Carel pRack pR300 and pR100TCompressor rack controller