All-in-one cold room controller with a large keypad, light and on/off keys, HACCP logging and add-on modules for three-phase units and electronic valves.
What it is: Cold room controller. LED and LCD keypad versions, with optional EVD EVO / EVD ice valve and 3PH power modules.
Key combo: Switch the controller off, then hold PRG for 2 s and enter the service password to reach the parameter categories.
Carel UltraCella error codes
| Code | Meaning | What to check |
|---|---|---|
| rE | Virtual control probe fault | Room / control probes and their wiring |
| E0–E4 | Probe B1 to B5 fault | That probe, its wiring and probe-type setting |
| LO / HI | Low / high temperature alarm | Room temperature, alarm thresholds AL / AH and delay |
| IA | Immediate external alarm | Device wired to the digital input |
| SA | Serious external alarm | Device wired to the digital input; outputs are switched off |
| Pd | Pump-down took too long | Liquid solenoid, low pressure switch, pump-down time setting |
| LP | Low pressure alarm | Refrigerant charge, low pressure switch, evaporator icing |
| AtS | Autostart in pump-down | Leaking solenoid valve letting pressure rise |
| CHt | High condenser temperature | Dirty condenser or condenser fan fault |
| dor | Door open too long | Door, door switch and its delay setting |
| Etc | Clock fault | Real time clock |
| EE / EF | Memory error (unit / operating parameters) | Reload parameters; replace the controller if it returns |
| Ed1 / Ed2 | Defrost ended on time (evaporator 1 / 2) | Heaters, defrost probe, defrost end temperature and maximum time |
| HA / HF | HACCP alarm (high temperature / after power cut) | Read and reset in the HACCP menu |
| LoG, uPL, dnL, SOF, ALM | USB download / upload / software update failed | USB stick and file; repeat the operation |
| SHA, LOA, MOA, LSA, Hit | EVD EVO protections: low superheat, LOP, MOP, low suction temperature, high condensing | Valve driver settings, charge, condenser |
| EEA | EVD EVO valve motor fault | Valve cable and motor |
| ES1–ES4 | EVD EVO probe S1 to S4 fault or out of range | Driver probes and wiring |
| bAt | EVD EVO battery flat or disconnected | Ultracap / battery module |
| EEE, EIC, EEC, EFu, ECn, ELE | EVD EVO memory error, valve not fully closed, emergency closing, firmware mismatch, configuration error, driver offline | Driver module, its firmware and connection |
| EPE | 3PH module offline | Connection to the three-phase module |
| EP0, EP1, EP2 | 3PH module probe fault (Sd1, Sd2, Sc) | Probes on the 3PH module |
| EPn | 3PH module configuration fault | Module settings |
| EPM | 3PH module motor protector | Compressor overload |
| EPU | 3PH module high/low pressure or Kriwan trip | Pressure switches and compressor protection module |
| AUH / AUL | High / low humidity alarm | Humidity probe and thresholds |
| GH1–GH3, GH6, GL1–GL3, GA1, GA2 | Generic function alarms | The generic function configured by the installer |
| GL6 | Serious alarm from external contact (generic function) | Device on the input |
| IA1, IA2, IE1–IE8, IEE, ILE, IEC, IEM | EVD ice valve driver alarms (probes, MOP, LOP, low superheat, emergency closing, memory, offline, configuration, alignment) | EVD ice module and its connection |
How to enter service / parameter mode
- Press ON/OFF to switch the controller off.
- Hold PRG for 2 seconds. PAS (or PASS on the LCD model) asks for the password.
- Enter the service password with UP / DOWN and press SET.
- The first category (Pro, probes) shows. Press SET to open it, or UP / DOWN to pick another.
How to change and save a setting
- Scroll with UP or DOWN to the parameter.
- Press SET to show its value.
- Change it with UP or DOWN.
- Press SET to confirm and go back to the code.
- Press PRG to step back and leave. Switch the controller back on.
Other useful key presses
| Task | How |
|---|---|
| Change set point | Hold SET for 2 s, adjust with UP / DOWN, press SET. |
Notes
- Resets differ by alarm (automatic, manual or both); we have not listed them per code because the manual's table layout is hard to read reliably. Check the alarm table in the manual.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Carel UltraCella user manual (+0300083EN rel. 2.2). Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Carel pages
- Carel ir33 (refrigeration)Refrigeration controller
- Carel easy (PJEZ)Refrigeration thermostat
- Carel ir33 UniversalUniversal controller (heating, cooling, PID)
- Carel MPXPRODisplay case and cold room controller
- Carel MPXoneDisplay case and cold room controller
- Carel EVD evolutionElectronic expansion valve driver
- Carel pRack pR300 and pR100TCompressor rack controller