Carel pRack pR300 and pR100T

pCO-based controllers for compressor racks and condensers, up to two suction lines. Alarms are grouped by letter: A probes, B pressures and levels, C compressors, E valve drivers, F fans, G generic and clock, T maintenance, U configuration, W warnings.

What it is: Compressor rack controller. pR300 for standard racks and pR100T for transcritical CO2 racks. Both use the same ALA / ALB / ALC… code system.

Key combo: Use the graphic terminal menu. Higher menus need the maintenance or manufacturer password: enter the service password when asked.

Carel pRack pR300 and pR100T error codes

CodeMeaningReset
ALA01Discharge temperature probe faultAutomatic
ALA02Condensing pressure probe faultAutomatic
ALA03Outside temperature probe faultAutomatic
ALA04–ALA23Generic probe A to E fault on expansion boards PLB1 to PLB4Automatic
ALA24Suction pressure probe faultAutomatic
ALA25Suction temperature probe faultAutomatic
ALA26Room temperature probe faultAutomatic
ALA27Condensing pressure probe fault, line 2Automatic
ALA28Discharge temperature probe fault, line 2Automatic
ALA29Suction pressure probe fault, line 2Automatic
ALA30Suction temperature probe fault, line 2Automatic
ALA31Condensing pressure backup probe faultAutomatic
ALA32Condensing pressure backup probe fault, line 2Automatic
ALA33Suction pressure backup probe faultAutomatic
ALA34Suction pressure backup probe fault, line 2Automatic
ALA35Common oil temperature probe faultAutomatic
ALA36Common oil temperature probe fault, line 2Automatic
ALA39Discharge temperature probe fault, compressors 1 to 6Automatic
ALA40Discharge temperature probe fault, compressors 1 to 6, line 2Automatic
ALA41Oil temperature probe fault compressors 1 to 6, line 1Automatic
ALA42Oil temperature probe fault compressor 1, line 2Automatic
ALB01Low suction pressure from pressure switchSemiautomatic
ALB02High condensing pressure from pressure switchManual or automatic (set by parameter)
ALB03Low condensing pressure from probeAutomatic
ALB04High condensing pressure from probeAutomatic
ALB05Liquid levelAutomatic
ALB06Common oil differentialAutomatic
ALB07Common fan circuit breakerAutomatic
ALB08Low suction pressure from pressure switch, line 2Semiautomatic
ALB09High condensing pressure from pressure switch, line 2Manual or automatic (set by parameter)
ALB10Low condensing pressure from probe, line 2Automatic
ALB11High condensing pressure from probe, line 2Automatic
ALB12Liquid level, line 2Automatic
ALB13Common oil differential, line 2Automatic
ALB14Common fan circuit breaker, line 2Automatic
ALB15High suction pressure from probeAutomatic
ALB16Low suction pressure from probeAutomatic
ALB17High suction pressure from probe, line 2Automatic
ALB18Low suction pressure from probe, line 2Automatic
ALB21Shutdown to prevent high pressureManual
ALB22Shutdown to prevent high pressure, line 2Manual
ALE01EEV motor error on Driver 1Automatic
ALE02Low superheat on Driver 1Automatic
ALE03EEV motor error on Driver 2Automatic
ALE04Low superheat on Driver 2Automatic
ALE05EEPROM error on Driver 1 in PLB1Automatic
ALE07EEPROM error on Driver 1 in PLB3Automatic
ALE08EEPROM error on Driver 2 in PLB1Automatic
ALE10EEPROM error on Driver 2 in PLB3Automatic
ALE11Parameter transmission error on Driver 1Automatic
ALE12Parameter transmission error on Driver 2Automatic
ALE13FW compatibility error on Driver 1Automatic
ALE14FW compatibility error on Driver 2Automatic
ALF01Fan circuit breakerManual or automatic (set by parameter)
ALF02Fan circuit breaker, line 2Manual or automatic (set by parameter)
ALG01Clock errorAutomatic
ALG02Extended memory errorAutomatic
ALH01ChillBooster faultAutomatic
ALH02ChillBooster fault, line 2Automatic
ALO02pLAN faultAutomatic
ALT01Compressor maintenance requestManual
ALT02Compressor maintenance request, line 2Manual
ALT03ChillBooster maintenance requestManual
ALT04ChillBooster maintenance request, line 2Manual
ALU01Configuration not allowedAutomatic
ALU02Control probes missingAutomatic
ALW01High pressure prevent warningAutomatic
ALW02High pressure prevent warning, line 2Automatic
ALW03Compressor inverter warningAutomatic
ALW04Compressor inverter warning, line 2Automatic
ALW05Fan inverter warningAutomatic
ALW06Fan inverter warning, line 2Automatic
ALW07Envelope warning: refrigerant not compatible with compressor seriesAutomatic
ALW08Envelope warning: custom envelope not configuredAutomatic
ALW09Envelope warning: suction or condensing probes not configuredAutomatic
ALW10Low superheat warningAutomatic
ALW11Low superheat warning, line 2Automatic
ALW12Warning, ChillBooster operating without outside sensorAutomatic
ALW13Warning, ChillBooster operating without outside sensor, line 2Automatic
ALC01–ALC99Compressor alarms: each compressor has its own alarm inputs, line 1 then line 2Manual or automatic (set by parameter)
ALG11–ALG34Generic function alarms on PLB1 to PLB4Manual or automatic (set by parameter)

How to enter service / parameter mode

  1. Press the programming (PRG) key on the graphic terminal. A password prompt appears.
  2. Enter the service password. Access stays open for 5 minutes after the last key press.
  3. Pick the menu branch with UP / DOWN and press ENTER. What you see depends on the level: user, maintenance or manufacturer (shown as 1, 2 or 3 lines in the top right corner).

How to change and save a setting

  1. Move the cursor to the value with ENTER.
  2. Change it with UP / DOWN.
  3. Press ENTER to confirm and move on.
  4. Press ESC to go back.

Other useful key presses

TaskHow
Alarm listPress the alarm (bell) key to see active alarms and the reset option.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Carel pRack pR300 user manual (+0300025EN) and pRack pR100T user manual (+0300022EN rel. 1.0). Always check the manual for your exact model and software version.

ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.