pCO-based controllers for compressor racks and condensers, up to two suction lines. Alarms are grouped by letter: A probes, B pressures and levels, C compressors, E valve drivers, F fans, G generic and clock, T maintenance, U configuration, W warnings.
What it is: Compressor rack controller. pR300 for standard racks and pR100T for transcritical CO2 racks. Both use the same ALA / ALB / ALC… code system.
Key combo: Use the graphic terminal menu. Higher menus need the maintenance or manufacturer password: enter the service password when asked.
Carel pRack pR300 and pR100T error codes
| Code | Meaning | Reset |
|---|---|---|
| ALA01 | Discharge temperature probe fault | Automatic |
| ALA02 | Condensing pressure probe fault | Automatic |
| ALA03 | Outside temperature probe fault | Automatic |
| ALA04–ALA23 | Generic probe A to E fault on expansion boards PLB1 to PLB4 | Automatic |
| ALA24 | Suction pressure probe fault | Automatic |
| ALA25 | Suction temperature probe fault | Automatic |
| ALA26 | Room temperature probe fault | Automatic |
| ALA27 | Condensing pressure probe fault, line 2 | Automatic |
| ALA28 | Discharge temperature probe fault, line 2 | Automatic |
| ALA29 | Suction pressure probe fault, line 2 | Automatic |
| ALA30 | Suction temperature probe fault, line 2 | Automatic |
| ALA31 | Condensing pressure backup probe fault | Automatic |
| ALA32 | Condensing pressure backup probe fault, line 2 | Automatic |
| ALA33 | Suction pressure backup probe fault | Automatic |
| ALA34 | Suction pressure backup probe fault, line 2 | Automatic |
| ALA35 | Common oil temperature probe fault | Automatic |
| ALA36 | Common oil temperature probe fault, line 2 | Automatic |
| ALA39 | Discharge temperature probe fault, compressors 1 to 6 | Automatic |
| ALA40 | Discharge temperature probe fault, compressors 1 to 6, line 2 | Automatic |
| ALA41 | Oil temperature probe fault compressors 1 to 6, line 1 | Automatic |
| ALA42 | Oil temperature probe fault compressor 1, line 2 | Automatic |
| ALB01 | Low suction pressure from pressure switch | Semiautomatic |
| ALB02 | High condensing pressure from pressure switch | Manual or automatic (set by parameter) |
| ALB03 | Low condensing pressure from probe | Automatic |
| ALB04 | High condensing pressure from probe | Automatic |
| ALB05 | Liquid level | Automatic |
| ALB06 | Common oil differential | Automatic |
| ALB07 | Common fan circuit breaker | Automatic |
| ALB08 | Low suction pressure from pressure switch, line 2 | Semiautomatic |
| ALB09 | High condensing pressure from pressure switch, line 2 | Manual or automatic (set by parameter) |
| ALB10 | Low condensing pressure from probe, line 2 | Automatic |
| ALB11 | High condensing pressure from probe, line 2 | Automatic |
| ALB12 | Liquid level, line 2 | Automatic |
| ALB13 | Common oil differential, line 2 | Automatic |
| ALB14 | Common fan circuit breaker, line 2 | Automatic |
| ALB15 | High suction pressure from probe | Automatic |
| ALB16 | Low suction pressure from probe | Automatic |
| ALB17 | High suction pressure from probe, line 2 | Automatic |
| ALB18 | Low suction pressure from probe, line 2 | Automatic |
| ALB21 | Shutdown to prevent high pressure | Manual |
| ALB22 | Shutdown to prevent high pressure, line 2 | Manual |
| ALE01 | EEV motor error on Driver 1 | Automatic |
| ALE02 | Low superheat on Driver 1 | Automatic |
| ALE03 | EEV motor error on Driver 2 | Automatic |
| ALE04 | Low superheat on Driver 2 | Automatic |
| ALE05 | EEPROM error on Driver 1 in PLB1 | Automatic |
| ALE07 | EEPROM error on Driver 1 in PLB3 | Automatic |
| ALE08 | EEPROM error on Driver 2 in PLB1 | Automatic |
| ALE10 | EEPROM error on Driver 2 in PLB3 | Automatic |
| ALE11 | Parameter transmission error on Driver 1 | Automatic |
| ALE12 | Parameter transmission error on Driver 2 | Automatic |
| ALE13 | FW compatibility error on Driver 1 | Automatic |
| ALE14 | FW compatibility error on Driver 2 | Automatic |
| ALF01 | Fan circuit breaker | Manual or automatic (set by parameter) |
| ALF02 | Fan circuit breaker, line 2 | Manual or automatic (set by parameter) |
| ALG01 | Clock error | Automatic |
| ALG02 | Extended memory error | Automatic |
| ALH01 | ChillBooster fault | Automatic |
| ALH02 | ChillBooster fault, line 2 | Automatic |
| ALO02 | pLAN fault | Automatic |
| ALT01 | Compressor maintenance request | Manual |
| ALT02 | Compressor maintenance request, line 2 | Manual |
| ALT03 | ChillBooster maintenance request | Manual |
| ALT04 | ChillBooster maintenance request, line 2 | Manual |
| ALU01 | Configuration not allowed | Automatic |
| ALU02 | Control probes missing | Automatic |
| ALW01 | High pressure prevent warning | Automatic |
| ALW02 | High pressure prevent warning, line 2 | Automatic |
| ALW03 | Compressor inverter warning | Automatic |
| ALW04 | Compressor inverter warning, line 2 | Automatic |
| ALW05 | Fan inverter warning | Automatic |
| ALW06 | Fan inverter warning, line 2 | Automatic |
| ALW07 | Envelope warning: refrigerant not compatible with compressor series | Automatic |
| ALW08 | Envelope warning: custom envelope not configured | Automatic |
| ALW09 | Envelope warning: suction or condensing probes not configured | Automatic |
| ALW10 | Low superheat warning | Automatic |
| ALW11 | Low superheat warning, line 2 | Automatic |
| ALW12 | Warning, ChillBooster operating without outside sensor | Automatic |
| ALW13 | Warning, ChillBooster operating without outside sensor, line 2 | Automatic |
| ALC01–ALC99 | Compressor alarms: each compressor has its own alarm inputs, line 1 then line 2 | Manual or automatic (set by parameter) |
| ALG11–ALG34 | Generic function alarms on PLB1 to PLB4 | Manual or automatic (set by parameter) |
How to enter service / parameter mode
- Press the programming (PRG) key on the graphic terminal. A password prompt appears.
- Enter the service password. Access stays open for 5 minutes after the last key press.
- Pick the menu branch with UP / DOWN and press ENTER. What you see depends on the level: user, maintenance or manufacturer (shown as 1, 2 or 3 lines in the top right corner).
How to change and save a setting
- Move the cursor to the value with ENTER.
- Change it with UP / DOWN.
- Press ENTER to confirm and move on.
- Press ESC to go back.
Other useful key presses
| Task | How |
|---|---|
| Alarm list | Press the alarm (bell) key to see active alarms and the reset option. |
Notes
- The list follows the pR300 manual. The pR100T adds CO2 codes: ALA43 gas cooler outlet temperature probe fault, ALA44 CO2 receiver pressure probe fault, ALA45 gas cooler outlet backup probe fault, extra warnings ALW14–ALW22 (probe type not allowed, auto-configuration error, oil receiver levels, valve driver probe, memory, motor, offline and battery) and more maintenance requests (ALT07–ALT18).
- On the pR100T, ALB03 / ALB04 refer to low / high gas cooler outlet temperature rather than condensing pressure.
- Compressor alarm meanings (ALC) depend on how each alarm input was set up on the rack. Check the compressor alarm configuration screens.
- Our check of the pR100T table found ALA02 described the same as ALA01. Confirm on the unit.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Carel pRack pR300 user manual (+0300025EN) and pRack pR100T user manual (+0300022EN rel. 1.0). Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Carel pages
- Carel ir33 (refrigeration)Refrigeration controller
- Carel easy (PJEZ)Refrigeration thermostat
- Carel ir33 UniversalUniversal controller (heating, cooling, PID)
- Carel MPXPRODisplay case and cold room controller
- Carel MPXoneDisplay case and cold room controller
- Carel UltraCellaCold room controller
- Carel EVD evolutionElectronic expansion valve driver