Carel MPXone
Compact controller for showcases and cold rooms with an optional expansion valve driver and a main/secondary network of up to nine units (five on the Basic model). Codes are close to MPXPRO, with some differences in probe numbering.
What it is: Display case and cold room controller. Basic and Medium/Advanced versions. Successor to MPXPRO with Bluetooth and the APPLICA app.
Key combo: Hold PRG for 3 s, then enter the service password, to reach the parameter menus. Press ALARM briefly to view alarms; hold it 3 s to reset.
Carel MPXone error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| rE | Control probe fault | The probe used for control has failed or is not configured | Automatic. Cooling runs on the duty-cycle setting (c4) meanwhile. |
| E1 | Probe S1 fault | Probe open, shorted, unplugged or wrong probe type set | Automatic once the probe reads normally. Check wiring and the probe-type parameters. |
| E2 | Probe S2 fault | Probe open, shorted, unplugged or wrong probe type set | Automatic once the probe reads normally. Check wiring and the probe-type parameters. |
| E3 | Probe S3 fault | Probe open, shorted, unplugged or wrong probe type set | Automatic once the probe reads normally. Check wiring and the probe-type parameters. |
| E4 | Probe S4 fault | Probe open, shorted, unplugged or wrong probe type set | Automatic once the probe reads normally. Check wiring and the probe-type parameters. |
| E5 | Probe S5 fault | Probe open, shorted, unplugged or wrong probe type set | Automatic once the probe reads normally. Check wiring and the probe-type parameters. |
| E6 | Probe S6 fault | Probe open, shorted, unplugged or wrong probe type set | Automatic once the probe reads normally. Check wiring and the probe-type parameters. |
| E11–E14 | Serial probe S11 to S14 not updated | Value sent over the network has stopped updating | Automatic. Check the network and the unit sending the value. |
| LO | Low temperature alarm | Alarm probe below the AL threshold for longer than Ad | Resets by itself once the cause clears. |
| HI | High temperature alarm | Alarm probe above the AH threshold for longer than Ad | Resets by itself once the cause clears. |
| LO2 | Second low temperature alarm | Below the AL2 threshold (probe set by AA2) | Resets by itself once the cause clears. |
| HI2 | Second high temperature alarm | Above the AH2 threshold (probe set by AA2) | Resets by itself once the cause clears. |
| IA | Immediate external alarm | Digital input set as immediate alarm has opened | Automatic. Cooling runs on duty setting A6. |
| dA | Delayed external alarm | Digital input set as delayed alarm stayed open past A7 | Automatic. Cooling runs on duty setting A6 if A7 is not 0. |
| dor | Door open too long | Door switch open past the door alarm delay | Resets by itself once the cause clears. |
| Etc | Real time clock fault | Clock not set or failed | Set the clock; replace the controller if it returns. |
| LSH | Low superheat | Expansion valve overfeeding (EEV models) | Automatic. Check superheat set point, probes and valve. |
| LSA | Low suction temperature | Suction temperature below its threshold too long (EEV models) | Automatic or manual depending on setting. |
| MOP | Maximum operating pressure | Evaporating pressure too high (EEV models) | Automatic. |
| LOP | Low evaporating temperature | Evaporating temperature too low (EEV models) | Automatic. |
| bLo | Valve blocked | Electronic valve appears stuck (EEV models) | Manual reset; disabled when P14 = 0. |
| Edc | Stepper driver communication error | Lost contact with the valve driver | Automatic. Check driver wiring. |
| HA | HACCP alarm type HA | High temperature during normal running for longer than the HACCP delay | Manual. Read and reset in the HACCP menu. |
| HF | HACCP alarm type HF | High temperature after a power cut | Manual. Read and reset in the HACCP menu. |
| MA | Lost contact with main controller (on a secondary) | Network cable or address problem | Automatic once communication returns. |
| u1… | Lost contact with secondary unit 1, 2, 3… (on the main) | Network cable or address problem | Automatic once communication returns. |
| n1… | Alarm on network unit 1, 2, 3… | A unit in the network has its own alarm | Check the unit named. |
| GPE | Custom gas parameter error | Custom refrigerant settings invalid | Automatic once corrected. |
| dA1 / dA2 | EVD ice or mini driver: probe S1 / S2 fault | Probe on the separate valve driver failed | Automatic once fixed. |
| AFr | EVD ice or mini driver firmware too old | Driver firmware below 1.7 | Clears once compatible firmware is recognised. |
| GHI / GLO | Generic function above maximum / below minimum | A user-set generic monitor tripped | Automatic. |
How to enter service / parameter mode
- Hold PRG for 3 seconds.
- Enter the service password with UP / DOWN and press PRG to confirm.
- Choose a category (VIS, CtL, CMP, DEF, ALM, FAN, EVD, RTC…) and press PRG.
- Scroll to the parameter you need.
How to change and save a setting
- With the parameter showing, press PRG to display its value.
- Change it with UP or DOWN.
- Press PRG to save and return to the code.
- Hold PRG for 3 s to go back a level.
Other useful key presses
| Task | How |
|---|---|
| View alarms | Press ALARM briefly, then UP / DOWN to scroll. |
| Reset alarms | Hold ALARM for 3 s. |
| First start-up | A set-up wizard asks for refrigerant type (PH) and basic settings; press PRG at the end. |
Notes
- A permanent Err on the display points to a faulty display or controller.
- The Basic model is limited to five network units, so only u1–u5 and n1–n5 apply.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Carel MPXone user manual (+0300086EN rel. 2.1) and MPXone instruction sheet (+0500140EN). Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Carel pages
- Carel ir33 (refrigeration)Refrigeration controller
- Carel easy (PJEZ)Refrigeration thermostat
- Carel ir33 UniversalUniversal controller (heating, cooling, PID)
- Carel MPXPRODisplay case and cold room controller
- Carel UltraCellaCold room controller
- Carel EVD evolutionElectronic expansion valve driver
- Carel pRack pR300 and pR100TCompressor rack controller