Carel MPXone

Compact controller for showcases and cold rooms with an optional expansion valve driver and a main/secondary network of up to nine units (five on the Basic model). Codes are close to MPXPRO, with some differences in probe numbering.

What it is: Display case and cold room controller. Basic and Medium/Advanced versions. Successor to MPXPRO with Bluetooth and the APPLICA app.

Key combo: Hold PRG for 3 s, then enter the service password, to reach the parameter menus. Press ALARM briefly to view alarms; hold it 3 s to reset.

Carel MPXone error codes

CodeMeaningLikely causeHow to reset
rEControl probe faultThe probe used for control has failed or is not configuredAutomatic. Cooling runs on the duty-cycle setting (c4) meanwhile.
E1Probe S1 faultProbe open, shorted, unplugged or wrong probe type setAutomatic once the probe reads normally. Check wiring and the probe-type parameters.
E2Probe S2 faultProbe open, shorted, unplugged or wrong probe type setAutomatic once the probe reads normally. Check wiring and the probe-type parameters.
E3Probe S3 faultProbe open, shorted, unplugged or wrong probe type setAutomatic once the probe reads normally. Check wiring and the probe-type parameters.
E4Probe S4 faultProbe open, shorted, unplugged or wrong probe type setAutomatic once the probe reads normally. Check wiring and the probe-type parameters.
E5Probe S5 faultProbe open, shorted, unplugged or wrong probe type setAutomatic once the probe reads normally. Check wiring and the probe-type parameters.
E6Probe S6 faultProbe open, shorted, unplugged or wrong probe type setAutomatic once the probe reads normally. Check wiring and the probe-type parameters.
E11–E14Serial probe S11 to S14 not updatedValue sent over the network has stopped updatingAutomatic. Check the network and the unit sending the value.
LOLow temperature alarmAlarm probe below the AL threshold for longer than AdResets by itself once the cause clears.
HIHigh temperature alarmAlarm probe above the AH threshold for longer than AdResets by itself once the cause clears.
LO2Second low temperature alarmBelow the AL2 threshold (probe set by AA2)Resets by itself once the cause clears.
HI2Second high temperature alarmAbove the AH2 threshold (probe set by AA2)Resets by itself once the cause clears.
IAImmediate external alarmDigital input set as immediate alarm has openedAutomatic. Cooling runs on duty setting A6.
dADelayed external alarmDigital input set as delayed alarm stayed open past A7Automatic. Cooling runs on duty setting A6 if A7 is not 0.
dorDoor open too longDoor switch open past the door alarm delayResets by itself once the cause clears.
EtcReal time clock faultClock not set or failedSet the clock; replace the controller if it returns.
LSHLow superheatExpansion valve overfeeding (EEV models)Automatic. Check superheat set point, probes and valve.
LSALow suction temperatureSuction temperature below its threshold too long (EEV models)Automatic or manual depending on setting.
MOPMaximum operating pressureEvaporating pressure too high (EEV models)Automatic.
LOPLow evaporating temperatureEvaporating temperature too low (EEV models)Automatic.
bLoValve blockedElectronic valve appears stuck (EEV models)Manual reset; disabled when P14 = 0.
EdcStepper driver communication errorLost contact with the valve driverAutomatic. Check driver wiring.
HAHACCP alarm type HAHigh temperature during normal running for longer than the HACCP delayManual. Read and reset in the HACCP menu.
HFHACCP alarm type HFHigh temperature after a power cutManual. Read and reset in the HACCP menu.
MALost contact with main controller (on a secondary)Network cable or address problemAutomatic once communication returns.
u1…Lost contact with secondary unit 1, 2, 3… (on the main)Network cable or address problemAutomatic once communication returns.
n1…Alarm on network unit 1, 2, 3…A unit in the network has its own alarmCheck the unit named.
GPECustom gas parameter errorCustom refrigerant settings invalidAutomatic once corrected.
dA1 / dA2EVD ice or mini driver: probe S1 / S2 faultProbe on the separate valve driver failedAutomatic once fixed.
AFrEVD ice or mini driver firmware too oldDriver firmware below 1.7Clears once compatible firmware is recognised.
GHI / GLOGeneric function above maximum / below minimumA user-set generic monitor trippedAutomatic.

How to enter service / parameter mode

  1. Hold PRG for 3 seconds.
  2. Enter the service password with UP / DOWN and press PRG to confirm.
  3. Choose a category (VIS, CtL, CMP, DEF, ALM, FAN, EVD, RTC…) and press PRG.
  4. Scroll to the parameter you need.

How to change and save a setting

  1. With the parameter showing, press PRG to display its value.
  2. Change it with UP or DOWN.
  3. Press PRG to save and return to the code.
  4. Hold PRG for 3 s to go back a level.

Other useful key presses

TaskHow
View alarmsPress ALARM briefly, then UP / DOWN to scroll.
Reset alarmsHold ALARM for 3 s.
First start-upA set-up wizard asks for refrigerant type (PH) and basic settings; press PRG at the end.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Carel MPXone user manual (+0300086EN rel. 2.1) and MPXone instruction sheet (+0500140EN). Always check the manual for your exact model and software version.

ServiceModes is not affiliated with Carel or any other manufacturer. Written in our own words from the manufacturer's documentation.