Tecnologic TLZ 11 and TLZ 11 P

4-digit on/off thermostat with a control relay (OUT), optional alarm relay (AL), one PTC/NTC probe and a digital input, for heating or cooling.

What it is: Heat/cool thermostat. The TLZ 11 P (high-temperature) version uses the same parameters but takes a Pt1000 or high-temperature NTC probe (SEnS = Pt10 or Entc, default Pt10).

Key combo: Hold P for about 5 s for the parameters. Power up while holding P for the hidden level.

Tecnologic TLZ 11 and TLZ 11 P error codes

CodeMeaningLikely causeHow to reset
E1 / −E1Probe faultProbe open or shorted, or reading outside the allowed rangeOUT follows tonE / toFE. Check wiring and the probe. Clears once the reading is valid.
EEPrMemory errorInternal memory faultCheck and re-enter the parameters.
odPower-on delay runningod time counting after power-upInformation only.
HIHigh temperature alarmAbove SP + HALClears below the threshold less dAL.
LOLow temperature alarmBelow SP − LALClears above the threshold plus dAL.
ALDigital input alarmInput set as external alarm (diF = 3) is activeClears when the input returns to normal.

How to enter service / parameter mode

  1. Hold P for about 5 seconds until the SET LED lights and the first code shows.
  2. If a password is set (PASS), 0 shows with the SET LED flashing: enter your password with up/down and press P.
  3. Hidden level (all parameters, and the way to read a forgotten PASS): switch off, hold P, switch on still holding P, and keep holding about 5 s.

Parameter list

CodeWhat it doesRangeDefault / typical
SPLLLowest set point−58.0 to SPHL−50.0
SPHLHighest set pointSPLL to 302.0100.0
SEnSProbe typePtc / ntcPtc
OFSProbe offset−30.0 to 30.00.0
UnitUnits°C / °F°C
dPDecimal pointOn / OFFOn
FiLReading filterOFF to 20.0 s2.0
HSEtDifferential0.0 to 30.02.0
tonEOUT on time with probe fault (OFF = stays off)OFF to 99.59 min.sOFF
toFEOUT off time with probe fault (OFF with tonE set = stays on)OFF to 99.59 min.sOFF
FuncOutput modeHEAt / CooLCooL
PSCCompressor protection type1 delay at switch-on, 2 delay after switch-off, 3 delay between starts1
PtCCompressor protection timeOFF to 99.59 min.sOFF
odOutput delay at power-upOFF to 99.59 min.sOFF
HALHigh alarm, offset above SPOFF to 100.0OFF
LALLow alarm, offset below SPOFF to 100.0OFF
dALAlarm differential0.0 to 30.02.0
ALdAlarm delayOFF to 99.59 min.sOFF
PALAlarm delay at power-upOFF to 24.00 h.min2.00
USrbU key functionOFF none, 1 on / stand-byOFF
diFDigital input−3 to 3: 3 = external alarm, 0 to 2 = no function0
PASSParameter password (OFF = none)OFF to 9999OFF
SPSet pointSPLL to SPHL0.0

How to change and save a setting

  1. Pick a code with up/down and press P: the code and value alternate.
  2. Change it with up/down and press P to store.
  3. Leave it about 20 s, or hold up or down, to exit.
  4. In the hidden level, press U to toggle a parameter between visible (SET LED on) and hidden (off).

Other useful key presses

TaskHow
Change set pointTap P (SP alternates with value), adjust with up/down, tap P or wait 15 s
On / stand-byPress U (with USrb = 1). The unit keeps its state through a power cut
Copy settingsKEY 01 programming key; see its own instructions

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Tecnologic TLZ 11 operating instructions (ISTR 06456, Vr.01) and TLZ 11 P high-temperature version, Tecnologic UK copies. Always check the manual for your exact model and software version.