Tecnologic TLZ 12

4-digit cooling/heating thermostat like the TLZ 11 with added defrost interval and length, defrost display lock and defrost control from the digital input.

What it is: Refrigeration controller with defrost. Same keypad, probe and alarm settings as the TLZ 11, plus timed defrost.

Key combo: Hold P about 5 s for parameters. Hold UP/DEFROST about 5 s for a manual defrost.

Tecnologic TLZ 12 error codes

CodeMeaningLikely causeHow to reset
E1 / −E1Probe faultProbe open or shorted, or reading outside the allowed rangeOUT follows tonE / toFE. Check wiring and the probe.
EEPrMemory errorInternal memory faultCheck and re-enter the parameters.
odPower-on delay runningod time counting after power-upInformation only.
dEFDefrost running (dLo = Lb)Timed, manual or input-started defrostInformation only.
PdEFAfter-defrost period (dLo = Lb)Display held until the reading comes back within Etdu of the set pointInformation only.
HIHigh temperature alarmAbove SP + HALClears below the threshold less dAL.
LOLow temperature alarmBelow SP − LALClears above the threshold plus dAL.
ALDigital input alarmInput set as external alarm (diF = 3) activeClears when the input returns to normal.

How to enter service / parameter mode

  1. Hold P for about 5 seconds until the SET LED lights and the first code shows.
  2. If a password is set (PASS), enter it with up/down and press P.
  3. Hidden level: switch off, hold P, switch on still holding P, keep holding about 5 s.

Parameter list

CodeWhat it doesRangeDefault / typical
SPLLLowest set point−58.0 to SPHL−50.0
SPHLHighest set pointSPLL to 302.0100.0
SEnSProbe typePtc / ntcPtc
OFSProbe offset−30.0 to 30.00.0
UnitUnits°C / °F°C
dPDecimal pointOn / OFFOn
FiLReading filterOFF to 20.0 s2.0
HSEtDifferential0.0 to 30.02.0
tonEOUT on time with probe faultOFF to 99.59 min.sOFF
toFEOUT off time with probe faultOFF to 99.59 min.sOFF
FuncOutput modeHEAt / CooLCooL
dintDefrost interval (OFF = none)OFF to 24.00 h.min6.00
dEFEDefrost length0.01 to 99.59 min.s30.00
dCtInterval countsrt clock time, ct OUT on timert
dLoDisplay in defrostOFF live, On frozen reading, Lb dEF / PdEF labelsOFF
EtduUnlock display within this of SP after defrost0.0 to 30.02.0
PSCCompressor protection type1 delay at switch-on, 2 delay after switch-off, 3 delay between starts1
PtCCompressor protection timeOFF to 99.59 min.sOFF
odOutput delay at power-upOFF to 99.59 min.sOFF
HALHigh alarm, offset above SPOFF to 100.0OFF
LALLow alarm, offset below SPOFF to 100.0OFF
dALAlarm differential0.0 to 30.02.0
ALdAlarm delayOFF to 99.59 min.sOFF
PALAlarm delay at power-upOFF to 24.00 h.min2.00
dALdAlarm and display hold after defrostOFF to 24.00 h.min1.00
USrbU key functionOFF none, 1 on / stand-byOFF
diFDigital input1 start defrost, 2 end defrost, 3 external alarm, 0 none (negative values also listed)0
PASSParameter password (OFF = none)OFF to 9999OFF
SPSet pointSPLL to SPHL0.0

How to change and save a setting

  1. Pick a code with up/down and press P.
  2. Change it with up/down and press P to store.
  3. Wait about 20 s, or hold up or down, to exit.

Other useful key presses

TaskHow
Manual defrostHold UP/DEFROST about 5 s outside programming; DEF LED lights
Change set pointTap P, adjust, tap P or wait 15 s

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Tecnologic TLZ 12 operating instructions (ISTR 06416, Vr.01), Tecnologic UK copy. Always check the manual for your exact model and software version.