Eliwell EWCM 4120, 4150 and 4180

Pack controller for compressor racks with a suction (inlet) and condenser (outlet) circuit. Alarms show as Er codes; many are event alarms that switch to manual reset after repeated trips.

What it is: Compressor rack and condenser controller. Up to four compressors and four condenser fans, with inverter options.

Key combo: Use the programming menu and enter the installer (or manufacturer) password when asked. UP + DOWN together resets alarms.

Eliwell EWCM 4120, 4150 and 4180 error codes

CodeMeaningReset type
Er01Suction low pressure switchCounts trips: automatic until it repeats too often in the sample window, then manual
Er02Suction high pressure switchCounts trips: automatic until it repeats too often in the sample window, then manual
Er03Condenser low pressure switchCounts trips: automatic until it repeats too often in the sample window, then manual
Er04Condenser high pressure switchCounts trips: automatic until it repeats too often in the sample window, then manual
Er05Suction probe above maximum alarmCounts trips: automatic until it repeats too often in the sample window, then manual
Er06Suction probe below minimum alarmCounts trips: automatic until it repeats too often in the sample window, then manual
Er07Condenser probe above maximum alarmCounts trips: automatic until it repeats too often in the sample window, then manual
Er08Condenser probe below minimum alarmCounts trips: automatic until it repeats too often in the sample window, then manual
Er09–Er12Compressor 1 to 4 locked out (its safety input tripped)Counts trips: automatic until it repeats too often in the sample window, then manual. That compressor is left out of the rotation
Er13Continuous (inverter) compressor locked outCounts trips: automatic until it repeats too often in the sample window, then manual
Er14–Er17Fan 1 to 4 overloadCounts trips: automatic until it repeats too often in the sample window, then manual. That fan is left out
Er18Continuous or shared fan overloadCounts trips: automatic until it repeats too often in the sample window, then manual
Er19–Er23Run hours exceeded: compressors 1–4 and inverter compressor (limit CP17)Manual: reset the hours counter
Er24–Er28Run hours exceeded: fans 1–4 and inverter fan (limit Fn19)Manual: reset the hours counter
Er29General alarm (blocks the system)Manual
Er30Suction probe faultAutomatic
Er31Condenser probe faultAutomatic
Er33Clock communication error (clock broken)Automatic
Er34Clock not setAutomatic once the clock is set
Er35Configuration errorAutomatic once settings are corrected
Er37Alarm log fullManual: clear the log

How to enter service / parameter mode

  1. Open the programming menu from the keypad.
  2. Enter the installer password (or manufacturer password) when asked.
  3. Browse folders and parameters with UP / DOWN; SET opens and confirms.

How to change and save a setting

  1. Select the parameter and press SET.
  2. Change the value with UP / DOWN.
  3. Press SET to save.

Other useful key presses

TaskHow
Reset alarmsPress UP + DOWN together. A manual alarm that is still active must clear first.
Silence the alarm relayPress any key; the alarm light then flashes.
Show probe readingsHold FNC to pick which reading the main display shows.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Eliwell EWCM 4120/4150/4180 user manual. Always check the manual for your exact model and software version.