Eliwell FREE Smart (SMP/SMD) cold room application
Cold room control on the FREE Smart platform: temperature, defrost, evaporator fans, humidity, thermal profile programs and alarms.
What it is: Programmable controller, cold room app. Applies only when the FREE Smart is running Eliwell's standard cold room application; custom programs use different codes.
Key combo: esc + set together opens the menu; the parameter folders need the access code entered in PASS first.
Eliwell FREE Smart (SMP/SMD) cold room application error codes
| Code | What it does | Range | Default |
|---|---|---|---|
| E1 | Room probe (Pb1) fault | Probe reading out of range, open or shorted | Compressor runs on the ONT/OFT timed cycle; heating and temperature alarms off. Clears when the probe reads again. |
| E2 | Evaporator probe (Pb2) fault | Probe out of range, open or shorted | Defrost ends on time only; fans follow the compressor. |
| E3 | Humidity probe (Pb3) fault | Probe out of range or faulty | Humidity control and humidity alarms switched off. |
| E4 | Cut-off feedback probe (Pb4) fault | Probe out of range or faulty | Cut-off output held off or at full, as set by F20. |
| 01 | External alarm | Digital input set as external alarm is active | Clears when the input goes off; regulators may be locked per rLO. |
| 02 | Panic alarm | Digital input set as panic alarm (someone trapped) is active | Clears when the input goes off. |
| 03 | Door open | Door open longer than tdO | Clears when the door shuts. |
| 04 | Pressure switch alarm | Pressure switch input tripped | See the pressure switch settings in the manual. |
| 08 / 09 | High / low room temperature | Pb1 beyond HAL or LAL | Warning only. Clears once temperature is back inside the limit. |
| 13 | Defrost timeout | Defrost ended on time, not on end temperature | Warning only; needs a manual reset. |
| 19 / 20 | High / low humidity | Pb3 beyond HHA or LHA | Warning only. Clears once humidity is back inside the limit. |
| RTC | Clock error | Real-time clock fault | Timed defrosts and program start times stop working. See the installation manual. |
How to enter service / parameter mode
- Press esc and set together to open the menu.
- Press UP to reach PASS, press set and enter the access code with UP/DOWN (from the manual), then confirm with set.
- Press esc + set again to enter PAr; set opens the first folder.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| SEt1 | Room set point | LSE to HSE °C | 0.0 |
| diF | Differential | 0.0 to 30.0 °C | 2.0 |
| HSE | Highest allowed set point | LSE to 110.0 °C | 50.0 |
| LSE | Lowest allowed set point | -50.0 to HSE °C | -50.0 |
| OSP | Economy offset added to set point | -30.0 to 30.0 °C | 0.0 |
| HC | Heat or cool mode | 0 = heat, 1 = cool | 1 |
| Ont / OFt | Compressor on / off time when Pb1 fails | 0 to 255 min | 10 / 10 |
| dOn | Compressor start delay | 0 to 1000 s | 10 |
| dOF | Stop delay | 0 to 1000 s | 0 |
| dbi | Minimum time between starts | 0 to 255 min | 2 |
| AFd | Temperature alarm differential | 1.0 to 50.0 °C | 1.0 |
| HAL / LAL | High / low temperature alarm | °C | 50.0 / -50.0 |
| PAO | Temperature alarm block after power-up | 0 to 10 h | 3 |
| dAO | Temperature alarm block after defrost | 0 to 999 min | 60 |
| OAO | Temperature alarm block after door closes | 0 to 10 h | 1 |
| tdO | Door open alarm delay | 0 to 255 min | 10 |
| tAO | Temperature alarm delay | 0 to 255 min | 0 |
| HHA / LHA | High / low humidity alarm | %RH | 50.0 / -50.0 |
| dAt | Alarm on defrost timeout | 0 = no, 1 = yes | 0 |
How to change and save a setting
- Scroll with UP/DOWN to the parameter and press set to show its value.
- Change with UP/DOWN and press set to store.
Notes
- The manual's parameter numbers (e.g. 1081 HAL) are shown on the display only by their short names.
- HAL/LAL and HHA/LHA are relative to the set point by default (Ath = 1).
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Eliwell FREE Smart Cold Room Application user manual 9MA10259 v1.1. Always check the manual for your exact model and software version.