Eliwell FREE Smart (SMP/SMD) cold room application

Cold room control on the FREE Smart platform: temperature, defrost, evaporator fans, humidity, thermal profile programs and alarms.

What it is: Programmable controller, cold room app. Applies only when the FREE Smart is running Eliwell's standard cold room application; custom programs use different codes.

Key combo: esc + set together opens the menu; the parameter folders need the access code entered in PASS first.

Eliwell FREE Smart (SMP/SMD) cold room application error codes

CodeWhat it doesRangeDefault
E1Room probe (Pb1) faultProbe reading out of range, open or shortedCompressor runs on the ONT/OFT timed cycle; heating and temperature alarms off. Clears when the probe reads again.
E2Evaporator probe (Pb2) faultProbe out of range, open or shortedDefrost ends on time only; fans follow the compressor.
E3Humidity probe (Pb3) faultProbe out of range or faultyHumidity control and humidity alarms switched off.
E4Cut-off feedback probe (Pb4) faultProbe out of range or faultyCut-off output held off or at full, as set by F20.
01External alarmDigital input set as external alarm is activeClears when the input goes off; regulators may be locked per rLO.
02Panic alarmDigital input set as panic alarm (someone trapped) is activeClears when the input goes off.
03Door openDoor open longer than tdOClears when the door shuts.
04Pressure switch alarmPressure switch input trippedSee the pressure switch settings in the manual.
08 / 09High / low room temperaturePb1 beyond HAL or LALWarning only. Clears once temperature is back inside the limit.
13Defrost timeoutDefrost ended on time, not on end temperatureWarning only; needs a manual reset.
19 / 20High / low humidityPb3 beyond HHA or LHAWarning only. Clears once humidity is back inside the limit.
RTCClock errorReal-time clock faultTimed defrosts and program start times stop working. See the installation manual.

How to enter service / parameter mode

  1. Press esc and set together to open the menu.
  2. Press UP to reach PASS, press set and enter the access code with UP/DOWN (from the manual), then confirm with set.
  3. Press esc + set again to enter PAr; set opens the first folder.

Parameter list

CodeWhat it doesRangeDefault / typical
SEt1Room set pointLSE to HSE °C0.0
diFDifferential0.0 to 30.0 °C2.0
HSEHighest allowed set pointLSE to 110.0 °C50.0
LSELowest allowed set point-50.0 to HSE °C-50.0
OSPEconomy offset added to set point-30.0 to 30.0 °C0.0
HCHeat or cool mode0 = heat, 1 = cool1
Ont / OFtCompressor on / off time when Pb1 fails0 to 255 min10 / 10
dOnCompressor start delay0 to 1000 s10
dOFStop delay0 to 1000 s0
dbiMinimum time between starts0 to 255 min2
AFdTemperature alarm differential1.0 to 50.0 °C1.0
HAL / LALHigh / low temperature alarm°C50.0 / -50.0
PAOTemperature alarm block after power-up0 to 10 h3
dAOTemperature alarm block after defrost0 to 999 min60
OAOTemperature alarm block after door closes0 to 10 h1
tdODoor open alarm delay0 to 255 min10
tAOTemperature alarm delay0 to 255 min0
HHA / LHAHigh / low humidity alarm%RH50.0 / -50.0
dAtAlarm on defrost timeout0 = no, 1 = yes0

How to change and save a setting

  1. Scroll with UP/DOWN to the parameter and press set to show its value.
  2. Change with UP/DOWN and press set to store.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Eliwell FREE Smart Cold Room Application user manual 9MA10259 v1.1. Always check the manual for your exact model and software version.

ServiceModes is not affiliated with Eliwell or any other manufacturer. Written in our own words from the manufacturer's documentation.