Eliwell IDPlus and EWPlus 902, 961, 971, 974 (and ID 974)
Single-set-point panel controllers for cabinets and cold rooms. The 961 is thermostat only, 971 adds defrost, and 974 adds evaporator fans. Settings live in folders (CP, dEF, FAn, AL, Add, diS, CnF, FPr) behind two password levels.
What it is: Refrigeration controller. One page for IDPlus 902/961/971/974, the IDPlus -HC versions, EWPlus 961/971/974 and the older ID 974. They share the same alarm labels and folder-style menus.
Key combo: Hold SET for more than 5 s, then enter the user (PA1) or installer (PA2) password when asked.
Eliwell IDPlus and EWPlus 902, 961, 971, 974 (and ID 974) error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| E1 | Room (cold room) probe Pb1 fault | Probe open, shorted, unplugged, or reading outside its range | Clears when the probe reads normally. Check the probe type (H00) and wiring, then replace the probe. Compressor runs on the Ont / OFt duty cycle meanwhile. |
| E2 | Defrost probe Pb2 fault (971 / 974 only) | Probe open, shorted, unplugged, or reading outside its range | Clears when the probe reads normally. Check the probe type (H00) and wiring, then replace the probe. Defrost ends on time (dEt) meanwhile; fans follow FCO. |
| E3 | Third probe Pb3 fault | Probe open, shorted, unplugged, or reading outside its range | Clears when the probe reads normally. Check the probe type (H00) and wiring, then replace the probe. Only where Pb3 is fitted. |
| AH1 | High temperature alarm (Pb1) | Pb1 above HAL for longer than tAO | Clears when Pb1 drops back below the HAL limit. Logged in the AL folder. |
| AL1 | Low temperature alarm (Pb1) | Pb1 below LAL for longer than tAO | Clears when Pb1 rises back above the LAL limit. |
| EA | External alarm | Digital input set as external alarm (H11 = ±5) is active | Clears when the outside cause is removed. Control locks if rLO = y. |
| OPd | Door open alarm | Door input (H11 = ±4) open longer than tdO | Close the door. Controller behaviour while open is set by OAO. |
| Ad2 | Defrost ended on time | Pb2 did not reach the defrost end temperature before the time limit | Clears on the next defrost that ends on temperature. Check heaters and Pb2. |
| COH | Over-heating alarm (HC models) | Pb3 above the SA3 limit | Check the condenser / the area Pb3 measures. |
| nPA / PAL | General pressure switch alarm | Pressure switch input activated (nPA counts trips; PAL shows when the limit is reached) | Check the pressure switch circuit; PAL needs the cause cleared before running resumes. |
| HC n, tC n, bC n, bt n | HACCP-style logs for Pb3 (HC models) | Pb3 left its SLH–SHH band, or a blackout occurred; n is the event number | Records only. Clear them from the AL folder. |
How to enter service / parameter mode
- Hold SET for more than 5 seconds.
- If passwords are on, PA1 (user) or PA2 (installer) shows. Press SET and enter the service password with UP / DOWN, then press SET.
- User level: the first parameter shows. Installer level: the first folder shows (CP, dEF, FAn, AL…).
- Open a folder with SET and scroll the parameters with UP / DOWN.
How to change and save a setting
- Select the parameter and press SET to show its value.
- Change it with UP or DOWN.
- Press SET to save it.
- To leave, wait for the display to time out. Switch the controller off and on after changing configuration parameters.
Other useful key presses
| Task | How |
|---|---|
| Manual defrost | Hold UP for at least 5 seconds (971 / 974). |
| Silence buzzer | Press and release any key. |
| Machine status menu | Press and release SET to see SEt, Pb1, Pb2 and the AL folder with active alarms. |
| Copy Card | Installer level, folder FPr: UL uploads to the card, Fr formats it. Downloading happens at power-up with the card fitted. |
Notes
- E2 and the defrost alarm only apply to 971 / 974 models, which have a defrost probe.
- On the older ID 974, high and low temperature alarms do not show on the main display; look for AH1 / AL1 in the AL folder of the machine status menu.
- The -HC versions add the COH alarm and the Pb3 log entries.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Eliwell IDPlus 902/961/971/974 user manual, IDPlus 961/974 -HC manual, EWPlus 961/971/974 and 971/974 user manuals, and ID 974 instructions. Always check the manual for your exact model and software version.