Full Gauge MT-512Ri / MT-512Ri plus

Single-relay cooling controller with timed off-cycle defrost (the compressor simply stops), min/max log and key lock.

What it is: Refrigeration temperature controller. MT-512RiL / MT-512RiL plus are the 12/24 V versions. The plus adds an RS-485 port for Sitrad.

Key combo: Hold ▲ and ▼ together 2 s for the F menu (F01 asks for the access code). Hold ▼ 4 s for manual defrost.

Full Gauge MT-512Ri / MT-512Ri plus error codes

DisplayMeaning
ErrProbe disconnected or reading out of range
OFFControl switched off (works as a thermometer only)
dEF On / dEF OFFDefrost or cooling started by hand
LOC On / LOC OFFKeypad locked / unlocked
HotShown when F08 is set to its minimum: unit works in heating mode
rstMin/max log cleared
dEL / rEF / dEFStatus view: start-up delay / cooling / defrost (press ▲)

How to enter service / parameter mode

  1. Set point: hold SET 2 s until SEt shows, adjust with ▲/▼, press SET to store.
  2. Parameters: hold ▲ and ▼ together 2 s until Fun, then F01 shows. Press SET and enter the access code from the manual.
  3. Pick a function with ▲/▼, tap SET to see it, change it, tap SET to store.
  4. Hold SET until --- shows to leave.
  5. °C/°F: enter F01 with the separate unit code from the manual, then choose the unit (settings return to factory values).
  6. Unlock a locked keypad: power up while holding ▲ for 10 s until LOC OFF shows.

Parameter list

CodeWhat it doesRangeDefault / typical
F02Display offset-5.0 to 5.0 °C0
F03 / F04Lowest / highest set point the user may choose-50 to 200 °C (plus: to 75 °C)-50 / 75 °C
F05Differential0.1–20.0 °C1.0
F06Compressor restart delay0–999 s20 s
F07Cooling time between defrosts1–999 min240 min
F08Defrost time (minimum = heating mode)0–999 min30 min
F09Start in cooling (0) or defrost (1) at power-up0 / 10
F10Hold the display during defrostno / yesno
F11Delay before control starts at power-up0–240 min0
F12Extra time added to the first cycle0–240 min0
F13 (Ri)Compressor with a failed probe: off / on0 / 10
F13 (Ri plus)RS-485 network address1–2471
F14 (Ri)Probe filter (slows the reading)0–90
F15 (Ri)Hold time to lock the keys (14 = locking disabled)14–60 s14
F16 (Ri)Allow switching control off: never / only when unlocked / always0–20

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.