Full Gauge MT-543e plus

Four-output controller: each stage can cool or heat on its own set point, stage 3 can be a cyclic timer, stage 4 an alarm, plus a buzzer, soak (ramp) program and RS-485.

What it is: Four-stage temperature controller. The older MT-543Ri plus uses a different F numbering and is not covered here.

Key combo: Press ▲ and ▼ together to reach F01 (access code). Hold ▲ 2 s to silence the alarm/buzzer.

Full Gauge MT-543e plus error codes

DisplayMeaning
ErrProbe disconnected or reading out of range
OFFControl functions switched off
LOC On / LOC OFFFunctions locked / unlocked
eCALCalibration fault: contact Full Gauge
PPPPSettings need to be re-entered
inibAlarm output or buzzer silenced from the quick menu

How to enter service / parameter mode

  1. Set point: hold SET 2 s until SEt shows.
  2. Parameters: press ▲ and ▼ together, choose F01, press SET and enter the access code from the manual.
  3. Pick with ▲/▼, tap SET to view, change, tap SET to store. Hold SET until ---- to leave.
  4. Separate codes from the manual change the units and the probe type.
  5. The soak program is reached from the quick-access key (SOAK menu).

Parameter list

CodeWhat it doesRangeDefault / typical
F02Display offset-5 to 5 °C0
F03Stage 1: cooling (0) or heating (1)0 / 11
F04 / F05Stage 1 lowest / highest set point-50 to 200 °C-50 / 105
F06Stage 1 differential0.1–20 °C1
F07Stage 1 restart delay0–999 s0
F08Stage 2: cool or heat on SP2 (0/1) or on SP1 (2/3)0–30
F09 / F10Stage 2 lowest / highest set point-50 to 200 °C-50 / 105
F11 / F12Stage 2 differential / restart delay0.1–20 °C / 0–999 s1 / 0
F13Stage 3: cool/heat on SP3, timer, minimum ventilation, cool/heat on SP10–50
F14 / F15Stage 3 lowest / highest set point-50 to 200 °C-50 / 105
F16 / F17Stage 3 differential / restart delay0.1–20 °C / 0–999 s1 / 0
F18Stage 3 timer in seconds (0) or minutes (1)0 / 10
F19Delay before the stage 3 timer starts0–999 s5
F20 / F21Stage 3 timer on / off time0–9990 / 0
F22Timer mode (independent, linked to stage 1, etc.)0–50
F23Buzzer: alarm inside band / outside band / outside band around SP10–21
F24 / F25Buzzer lower / upper limit-50 to 200 °C-50 / 105
F26 / F27Buzzer on / off time0–999 s1 / 1
F28Buzzer block at power-up0–999 min0
F29Buzzer re-arm time after silencingAuto–999 minAuto
F30Stage 4: cool/heat on SP4, alarm inside/outside band, around SP1, cool/heat on SP10–63
F31 / F32Stage 4 lower / upper point-50 to 200 °C21 / 27
F33 / F34Stage 4 differential / restart delay0.1–20 °C / 0–999 s1 / 0
F35Alarm block at power-up0–999 min0
F36Alarm re-arm time after silencingAuto–999 minAuto
F37 / F38Alarm output on / off time0–999 s1 / 1
F39Alarm delayno–999 minno
F40 / F41Probe filter mode / strength0–1 / 0–20 s0 / 0
F42 / F43Lock mode / hold time to lock0–2 / 15–60 s0 / 15
F44Who may switch control offno–2no
F45Soak program on output 10 / 10
F46–F55Soak points 1–5: temperature and hold time-50 to 200 °C / 0–999 min23 °C / 0
F56RS-485 address1–2471

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Full Gauge MT-543e plus instruction manual. Always check the manual for your exact model and software version.