Full Gauge TC-900E power / TC-900E 2HP

Three-relay controller (compressor, defrost, fans) with up to three probes, economy set point, fast freezing, door input and condenser protection.

What it is: Refrigeration controller (cooling, defrost, fans). Both versions share the same menu and parameter list; they differ in relay rating.

Key combo: Press ▲ and ▼ together for F01 (access code). Hold ▼ 4 s for manual defrost. A scroll key opens the quick menu (defrost, eco, fast freeze, lock, control off).

Full Gauge TC-900E power / TC-900E 2HP error codes

DisplayMeaning
Err1Room (S1) probe disconnected or out of range
Err2Evaporator (S2) probe disconnected or out of range
Err3Third probe (S3) disconnected or out of range
Athi / AtloRoom temperature above F07 / below F47
AC1 / AC2Condenser too hot, first and second level (F49 / F44)
ALrCCompressor ran longer than F46 without reaching set point
ALrEAlarm from a digital input
Opn / AOPnDoor open / door open too long (F50)
eCORunning on the economy set point
OFFControl routines switched off
LOC On / LOC OFFSettings locked / unlocked
. (dot on display)Defrost ended on time, not on temperature
eCALCalibration fault: contact Full Gauge
PPPPSettings need to be re-entered
dEL / Fan / rEFr / Pre / dEFr / dRAiStatus: start delay / fan delay / cooling / pump-down / defrost / drip

How to enter service / parameter mode

  1. Set point: hold SET 2 s, change with ▲/▼, press SET.
  2. Parameters: press ▲ and ▼ together until F01 shows, tap SET and enter the access code from the manual. You can view settings without the code but not change them.
  3. Pick with ▲/▼, tap SET, change, tap SET to store. Long-press SET until ---- to leave.
  4. Unlock: power up holding ▲ for about 10 s until LOC OFF shows.
  5. A second code from the manual selects °C or °F.

Parameter list

CodeWhat it doesRangeDefault / typical
F02Differential (normal)0.1–20 °C2
F03Room probe offset-20 to 20 °C0
F04 / F05Lowest / highest user set point-50 to 105 °C-50 / 105
F06Start-up delayno–30 minno
F07High room alarm-50 to 105 °C105
F08Cooling time between defrosts1–999 min240
F09 / F10Minimum compressor on / off timeno–999 s0 / 0
F11Compressor with failed S1: off / on / cycle (F37–F38)0–21
F12Defrost at power-upno / yesno
F13Evaporator temperature that ends defrost-50 to 105 °C30
F14Maximum defrost timeno–90 min30
F15Fans on in defrostoff / onoff
F16Electric (0) or hot gas (1) defrost0 / 10
F17Hold display after defrostno–99 minno
F18Drip timeno–99 min1
F19 / F20Fan restart: evaporator temperature / maximum delay-50 to 105 °C / 0–30 min20 / 1
F21Fan mode0–74
F22Stop fans if evaporator above-50 to 105 °C30
F23Pump-down time before defrostno–999 minno
F24Room probe filter0–90
F25Time evaporator must stay cold before temperature defrost0–90 min0
F26 / F27Normal / economy set point-50 to 105 °C-15 / -10
F28Economy differential0.1–20 °C2
F29Door-closed time before economy modeno–999 minno
F30 / F31S3–S1 difference to enter / leave economy0.1–20 °C2 / 5
F32Maximum time in economyno–100 hno
F33 / F34Fast-freeze limit temperature / time-50 to 105 °C / no–999 min-25 / no
F35 / F36Fan on / off times1–99 min2 / 8
F37 / F38Compressor on / off time with failed S10–999 min0 / 0
F39Start defrost by time (0) or temperature (1)0 / 10
F40Door-open time that triggers a defrostno–999 minno
F41Evaporator temperature that starts defrost-50 to 105 °C-50
F42 / F43Door-open time to stop fans / all outputsno–999 minno
F44 / F45Condenser cut-out temperature / differentialno–105 °C / 0.1–20 °C55 / 5
F46Compressor run time without reaching set point before shutdownno–999 minno
F47Low room alarm-50 to 105 °C-50
F48Temperature alarm delayno–999 minno
F49Condenser alarm temperature0–105 °C45
F50Door-open alarm timeno–999 minno
F51Buzzeroff / onoff
F52Digital input 1 / S3 functionoff–13off
F53Digital input 2 functionoff–10off
F54 / F55S2 / S3 probe offset (S2 off = no evaporator probe)-20 to 20 °C0 / 0
F56Who may switch control offno–4no
F57 / F58Lock mode / hold time to lock0–2 / 15–60 s0 / 15

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Full Gauge TC-900E power and TC-900E 2HP instruction manuals. Always check the manual for your exact model and software version.