Elitech ECS-02CX

Small cabinet controller with a large compressor relay (up to 30 A), optional defrost relay and evaporator probe, and two-level (Pr1/Pr2) menus in Dixell style.

What it is: Refrigeration controller

Key combo: Set + down for 3 s for Pr1; keep holding past 7 s for the hidden Pr2 list.

Elitech ECS-02CX error codes

CodeMeaningLikely causeHow to reset
P1Cabinet probe faultProbe open or shortedAutomatic once fixed. Compressor cycles on Cy (run) / Cn (stop) meanwhile.
P2Evaporator probe faultProbe open or shortedAutomatic. Defrost runs on id and Md times.
HAHigh temperature alarmCabinet above AU after Ad (and dA at start-up)Clears below AU. Outputs unchanged.
LALow temperature alarmCabinet below AL after AdClears above AL. Outputs unchanged.
nPNo evaporator probeEvaporator reading requested but P2 = nInformation only.
ErHot key copy failedBad connection or keyCheck the key is seated and repeat.
oF / onKeypad locked / unlockedUp + down held 3 sHold up + down 3 s again.

How to enter service / parameter mode

  1. Hold Set + down for 3 seconds. The set light comes on: this is the user (Pr1) list.
  2. For every parameter, hold Set + down again for more than 7 s until L2 shows (Pr2, hidden list). If Pr1 is empty, nP shows; keep holding until L2.

Parameter list

CodeWhat it doesRangeDefault / typical
StSet pointLS to US3
HyHysteresis0.1 to 10 °C2
LSLowest set point−50 °C to St−50
USHighest set pointSt to 99 °C99
otCabinet probe offset−9.9 to 9.9 °C0
P2Evaporator probe fittedy / ny
oEEvaporator probe offset−9.9 to 9.9 °C0
odOutput delay at power-up0 to 99 min0
ACAnti-short-cycle delay0 to 50 min1
CyRun time with cabinet probe fault0 to 99 min15
CnStop time with cabinet probe fault0 to 99 min30
CHModeCL cooling, Ht heatingCL
CFUnitsC / FC
LdDefault displayP1 cabinet, P2 evaporator, SP set pointP1
dEDefrost end temperature−50 to 90 °C2
idDefrost interval (0 = none)0 to 99 h8
MdMaximum defrost time1 to 99 min20
dFDisplay in defrostrt live, it frozen, St set point, dF labelit
AUHigh alarmAL+1 to 99 °C99
ALLow alarm−50 °C to AU−1−50
AdAlarm delay0 to 99 min15
dAAlarm delay at start-up0 to 99 min90

How to change and save a setting

  1. Pick a code with up or down and press Set to show its value.
  2. Change it with up or down.
  3. Press Set to store and move on.
  4. Press Set + up, or wait 15 s, to exit.

Other useful key presses

TaskHow
Change set pointHold Set 2 s, adjust with up/down, press Set
Show evaporator temperatureTap the defrost key
Manual defrostHold the defrost key 2 s (again to stop)
Restore user valuesHold Set + up 10 s until rS shows
Copy to hot key (CPK-4)Insert the key and hold up until uP shows
Load from hot keyInsert the key and hold down until do shows, then power-cycle

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech ECS-02CX temperature controller instruction. Always check the manual for your exact model and software version.