Elitech EK-3020 / EK-3021
Six-key on/off cooling controllers with separate cut-in and cut-out set points and timed defrost (electric or hot gas).
What it is: Refrigeration temperature controller. EK-3020 has a cabinet probe only; EK-3021 adds a defrost (evaporator) probe with defrost end temperature F6 and settings H8/H9.
Key combo: Hold OK 1 s to unlock. Hold OK over 5 s for the F menu; from there hold OK over 5 s again for the hidden H menu (needs the access code).
Elitech EK-3020 / EK-3021 error codes
| Code | Meaning | Likely cause | What to do |
|---|---|---|---|
| E1 | Cabinet probe fault | Probe open or shorted | Compressor runs a fixed 30 min off / 15 min on cycle until fixed. |
| E2 | Defrost probe fault (EK-3021) | Probe open or shorted | Shown in turn with the cabinet temperature; defrost ends on time only. |
| E1 + E2 | Both probes failed (EK-3021) | Shown alternately. | |
| HA | High temperature alarm | Cabinet above On Temp + F11 (or H3) for longer than F12 | Clears once back in range. |
| LA | Low temperature alarm | Cabinet below Off Temp - F11 (or H4) for longer than F12 | Clears once back in range. |
| Err | Settings could not be saved | Memory write error | Power the controller off and on, then re-enter. |
How to enter service / parameter mode
- Press OK for 1 s to unlock (relocks after 30 s idle).
- Set points: press On Temp or Off Temp, adjust with ▲/▼; OK or 30 s idle saves.
- F menu: hold OK over 5 s until F1 shows. ▲/▼ to pick, OK to view and save.
- Hidden H menu: inside the F menu hold OK over 5 s, then enter the access code from the manual.
- Factory reset: while locked hold ▲ over 10 s until rES shows, then press OK within 3 s.
- Save your own preset: while locked hold On Temp 10 s (COP), press OK. Restore it: hold Off Temp 10 s (don), press OK.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| On Temp | Compressor cut-in temperature | Off Temp to 85.0 °C | 10.0 °C |
| Off Temp | Compressor cut-out temperature | -40.0 °C to On Temp | -10.0 °C |
| F1 | Defrost duration | 1–120 min | 30 min |
| F2 | Defrost interval (0 = off) | 0–120 h | 6 h |
| F3 | Interval counts controller time (0) or compressor time (1) | 0 / 1 | 1 |
| F4 | Drip time after defrost | 0–120 min | 3 min |
| F5 | Defrost type: electric (0) or hot gas (1) | 0 / 1 | 0 |
| F6 | Defrost end temperature (EK-3021 only) | -40.0 to 50.0 °C | 10 °C |
| F9 | Compressor restart delay | 0–10 min | 0 |
| F10 | Alarm block after power-up | 0–24.0 h | 2.0 h |
| F11 | Alarm band | 0–50.0 °C | 5.0 °C |
| F12 | Alarm delay | 0–120 min | 10 min |
| F13 | Cabinet probe offset | -10.0 to 10.0 °C | 0.0 |
| H1 / H2 | Compressor off / on time with a failed cabinet probe | 1–60 / 0–60 min | 30 / 15 min |
| H3 / H4 | Absolute high / low alarm (used when H5 = 0) | to 85.0 °C / from -40.0 °C | 20.0 / -20.0 °C |
| H5 | Alarm type: absolute (0) or relative to set points (1) | 0 / 1 | 1 |
| H6 | Buzzer on alarm | 0 / 1 | 1 |
| H7 | Display during defrost: temperature / dEF / start temperature | 0 / 1 / 2 | 0 |
| H8 | Defrost probe fitted (EK-3021) | 0 / 1 | 1 |
| H9 | Defrost probe offset (EK-3021) | -10.0 to 10.0 °C | 0.0 |
| H17 | Display decimals (0) or whole numbers (1) | 0 / 1 | 0 |
Notes
- With hot gas defrost the compressor pauses 3 min before defrost and restarts 2 min after it.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Elitech EK-3020 and EK-3021 user manuals (scanned, read by eye). Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Elitech or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Elitech pages
- Elitech ECS-180, ECS-180neo and ECS-2280neoRefrigeration controller
- Elitech STC-1000, STC-1000HX and STC-1000XHeat/cool thermostat
- Elitech STC-8000HX and STC-8080HXCooling thermostat
- Elitech STC-200+Cool/heat/alarm thermostat
- Elitech ECS-02CXRefrigeration controller
- Elitech ECS-06CXRefrigeration controller
- Elitech ECS-16Beverage cooler controller
- Elitech ECS-961neoRefrigeration controller
- Elitech ETC-902Heat/cool controller
- Elitech EK-3010 and EK-3010LCool room / heating controller
- Elitech EK-3030ECool room controller
- Elitech ECS-974neo and ETC-974ARefrigeration controller
- Elitech E-1000Heat/cool controller with lighting
- Elitech MTC-6040Temperature and humidity controller
- Elitech EK-3030Refrigeration temperature controller
- Elitech ECB-1000PLUS / ECB-1000PLUS CloudCold room control board
- Elitech ECB-LS230 (ECB-LS2xx split control box)Cold room control box
- Elitech LS-200 split control boxCold room control box
- Elitech STC-1000Pro TH / STC-1000WiFi THPlug-in temperature and humidity controller