Elitech ECS-16

Single-probe controller for drink coolers with a 30 A compressor relay, optional defrost relay (otherwise off-cycle defrost) and a heating mode.

What it is: Beverage cooler controller

Key combo: Hold Set for 3 s for the user menu. Administrator settings sit behind the Po access code.

Elitech ECS-16 error codes

CodeMeaningLikely causeHow to reset
E1Probe faultCabinet probe open or shortedOutput cycles on A1 (on) / A2 (off). A2 = 0 keeps it off. Clears once the probe reads.
dFDefrost runningTimed defrost (relay or off-cycle)Normal. Ends after d2.
drFactory values loadedOne-key recovery doneInformation only.

How to enter service / parameter mode

  1. Hold Set for 3 seconds: St shows. Press Set to view and adjust the set point.
  2. For the full list, step to Po with the light key, press Set and enter the administrator access code from the manual, then press Set.
  3. Press the light key: rd shows, meaning the administrator list is open. A wrong code just exits.

Parameter list

CodeWhat it doesRangeDefault / typical
StSet pointC3 to C44 °C
rdHysteresis1 to 15 °C3
C1Probe offset−10 to 10 °C−1
C2Output start delay0 to 60 min3
C3Lowest set point−50 °C to St2
C4Highest set pointSt to 85 °C10
A1On time with probe fault1 to 60 min15
A2Off time with probe fault (0 = stay off)0 to 60 min10
d1Defrost interval (0 = none)0 to 90 h6
d2Defrost time1 to 90 min20
d3Display in defrost0 live, 1 dF, 2 frozen reading2
HCMode0 cooling, 1 heating0

How to change and save a setting

  1. Pick a code with the light or rotate key and press Set.
  2. Adjust with the same keys and press Set to return to the list.
  3. Press the defrost (Rst) key, or wait 30 s, to save and exit.

Other useful key presses

TaskHow
Manual defrost on/offHold the defrost key 3 s (d1 not 0)
Factory resetHold rotate 10 s: H0 shows. Choose H1 or H2 preset and press the defrost key; dr confirms

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech ECS-16 temperature controller user manual. Always check the manual for your exact model and software version.