Elitech ECS-16
Single-probe controller for drink coolers with a 30 A compressor relay, optional defrost relay (otherwise off-cycle defrost) and a heating mode.
What it is: Beverage cooler controller
Key combo: Hold Set for 3 s for the user menu. Administrator settings sit behind the Po access code.
Elitech ECS-16 error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| E1 | Probe fault | Cabinet probe open or shorted | Output cycles on A1 (on) / A2 (off). A2 = 0 keeps it off. Clears once the probe reads. |
| dF | Defrost running | Timed defrost (relay or off-cycle) | Normal. Ends after d2. |
| dr | Factory values loaded | One-key recovery done | Information only. |
How to enter service / parameter mode
- Hold Set for 3 seconds: St shows. Press Set to view and adjust the set point.
- For the full list, step to Po with the light key, press Set and enter the administrator access code from the manual, then press Set.
- Press the light key: rd shows, meaning the administrator list is open. A wrong code just exits.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| St | Set point | C3 to C4 | 4 °C |
| rd | Hysteresis | 1 to 15 °C | 3 |
| C1 | Probe offset | −10 to 10 °C | −1 |
| C2 | Output start delay | 0 to 60 min | 3 |
| C3 | Lowest set point | −50 °C to St | 2 |
| C4 | Highest set point | St to 85 °C | 10 |
| A1 | On time with probe fault | 1 to 60 min | 15 |
| A2 | Off time with probe fault (0 = stay off) | 0 to 60 min | 10 |
| d1 | Defrost interval (0 = none) | 0 to 90 h | 6 |
| d2 | Defrost time | 1 to 90 min | 20 |
| d3 | Display in defrost | 0 live, 1 dF, 2 frozen reading | 2 |
| HC | Mode | 0 cooling, 1 heating | 0 |
How to change and save a setting
- Pick a code with the light or rotate key and press Set.
- Adjust with the same keys and press Set to return to the list.
- Press the defrost (Rst) key, or wait 30 s, to save and exit.
Other useful key presses
| Task | How |
|---|---|
| Manual defrost on/off | Hold the defrost key 3 s (d1 not 0) |
| Factory reset | Hold rotate 10 s: H0 shows. Choose H1 or H2 preset and press the defrost key; dr confirms |
Notes
- Defaults shown are the H1 preset. The H2 preset uses different values (for example St 3, rd 6, d1 12 h).
- In heating mode set d1 to 0 so no defrost runs.
- Whole-degree display only.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Elitech ECS-16 temperature controller user manual. Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Elitech or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Elitech pages
- Elitech ECS-180, ECS-180neo and ECS-2280neoRefrigeration controller
- Elitech STC-1000, STC-1000HX and STC-1000XHeat/cool thermostat
- Elitech STC-8000HX and STC-8080HXCooling thermostat
- Elitech STC-200+Cool/heat/alarm thermostat
- Elitech ECS-02CXRefrigeration controller
- Elitech ECS-06CXRefrigeration controller
- Elitech ECS-961neoRefrigeration controller
- Elitech ETC-902Heat/cool controller
- Elitech EK-3010 and EK-3010LCool room / heating controller
- Elitech EK-3030ECool room controller
- Elitech ECS-974neo and ETC-974ARefrigeration controller
- Elitech E-1000Heat/cool controller with lighting
- Elitech MTC-6040Temperature and humidity controller
- Elitech EK-3030Refrigeration temperature controller
- Elitech EK-3020 / EK-3021Refrigeration temperature controller
- Elitech ECB-1000PLUS / ECB-1000PLUS CloudCold room control board
- Elitech ECB-LS230 (ECB-LS2xx split control box)Cold room control box
- Elitech LS-200 split control boxCold room control box
- Elitech STC-1000Pro TH / STC-1000WiFi THPlug-in temperature and humidity controller