Three-relay cabinet controller (compressor, defrost, fan) with cabinet and evaporator probes, electric / hot gas / off-cycle defrost and relative high and low alarms.
What it is: Refrigeration controller. Same parameter list on both. Defaults below are the ECS-974neo values; the ETC-974A differences are in the notes.
Key combo: Tap SET for the set point. Hold SET (5 s on the neo, 3 s on the ETC-974A) for PA1 and the administrator list.
Elitech ECS-974neo and ETC-974A error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| E1 | Cabinet probe fault | Probe open or shorted | Compressor follows Ont / OFt: Ont 0 = off, OFt 0 = on, both set = duty cycle. |
| E2 | Evaporator probe fault | Probe open or shorted | Defrost ends on time (dEt). Fans no longer follow the evaporator temperature. |
| AH1 | High temperature alarm | Cabinet above SEt + HAL after the alarm delay | Clears below SEt + HAL. |
| AL1 | Low temperature alarm | Cabinet below SEt − LAL after the alarm delay | Clears when the cabinet warms back up. |
| Er | Copy card failed | Card not seated or faulty | Reseat and repeat. |
| EP | Copy card data does not match | Card from another model | Use the right card or upload to it first. |
| rSt | Reset done | Up + down held 10 s | Loaded the backup copy of settings. |
| LOC | Set point locked | LOC = y | Change LOC in the administrator list. |
How to enter service / parameter mode
- Hold SET until PA1 shows. If PA1 is 0 the list opens directly.
- Otherwise press SET (00 shows), enter the administrator access code with up/down and press SET. Correct code: the list starts at diF. Wrong code: the controller exits.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| SEt | Set point | LSE to HSE | 4.0 °C |
| diF | Differential | 0.1 to 30.0 °C | 2.0 |
| HSE | Highest set point | SEt to 99.0 °C | 90.0 |
| LSE | Lowest set point | −50.0 °C to SEt | −50.0 |
| Ont | Compressor on time with probe fault | 0 to 250 min | 0 |
| OFt | Compressor off time with probe fault | 0 to 250 min | 1 |
| dOF | Minimum off time before restart | 0 to 250 min | 0 |
| OdO | Output delay at power-up | 0 to 250 min | 0 |
| dty | Defrost type | 0 electric, 1 hot gas (reverse cycle), 2 off-cycle | 0 |
| dit | Defrost interval | 1 to 250 h | 6 |
| dCt | Interval counts | 0 compressor run hours, 1 clock time, 2 compressor off hours | 1 |
| dOH | First defrost delay after power-up | 1 to 59 min | 1 |
| dEt | Maximum defrost time (0 = no defrost) | 0 to 250 min | 30 |
| H42 | Evaporator probe fitted | n / y | y |
| dSt | Defrost end temperature | −50 to 99 °C | 8.0 |
| dPO | Defrost at power-up | n / y | n |
| FSt | Fan stop temperature (evaporator) | −50 to 99 °C | 2.0 |
| FAd | Fan restart differential | 1.0 to 50.0 °C | 2.0 |
| Fdt | Fan delay after defrost | 0 to 250 min | 0 |
| dt | Drip time | 1 to 250 min | 1 |
| dFd | Fans run during defrost | n / y | y |
| FCO | Fans run with compressor off | n / y | y |
| HAL | High alarm offset above SEt | 0.1 to 20.0 °C | 4.0 |
| LAL | Low alarm offset below SEt | 0.1 to 20.0 °C | 4.0 |
| PAO | Alarm hold-off after power-up | 0 to 15 h | 0 |
| dAO | Alarm hold-off after defrost | 0 to 250 min | 0 |
| tAO | Temperature alarm delay | 0 to 250 min | 0 |
| LOC | Lock set point | n / y | n |
| PA1 | Administrator access code (set your own) | 0 to 250 | see manual |
| ndt | Show decimals | n / y | y |
| CA1 | Cabinet probe offset | −12.0 to 12.0 °C | 0 |
| CA2 | Evaporator probe offset | −12.0 to 12.0 °C | 0 |
| ddL | Display in defrost | 0 live, 1 frozen until SEt reached, 2 dEF until SEt reached | 1 |
How to change and save a setting
- Pick the code with up/down and press SET.
- Change it with up/down and press SET to return to the list.
- Press the exit key, or wait 30 s, to save and exit.
Other useful key presses
| Task | How |
|---|---|
| Show evaporator temperature | Tap the defrost key |
| Manual defrost / step cooling → defrost → drip | Hold the defrost key 3 s |
| Reset to backup copy | Hold up + down 10 s until rSt |
| Copy card | Card in, hold up 3 s (uP, upload) or down 3 s (do, download), wait 5 s, remove, power-cycle |
Notes
- ETC-974A differences: HSE default 99.0, drip time dt 0 to 250 min (default 0), HAL/LAL default 2.0 °C, and the administrator list opens after a 3 s hold.
- Fans: with the evaporator probe working they run below FSt − FAd and stop above FSt.
- Hot gas: four-way valve output opens during defrost and drip with the compressor on in defrost.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Elitech ECS-974neo and ETC-974A user manuals. Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Elitech or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Elitech pages
- Elitech ECS-180, ECS-180neo and ECS-2280neoRefrigeration controller
- Elitech STC-1000, STC-1000HX and STC-1000XHeat/cool thermostat
- Elitech STC-8000HX and STC-8080HXCooling thermostat
- Elitech STC-200+Cool/heat/alarm thermostat
- Elitech ECS-02CXRefrigeration controller
- Elitech ECS-06CXRefrigeration controller
- Elitech ECS-16Beverage cooler controller
- Elitech ECS-961neoRefrigeration controller
- Elitech ETC-902Heat/cool controller
- Elitech EK-3010 and EK-3010LCool room / heating controller
- Elitech EK-3030ECool room controller
- Elitech E-1000Heat/cool controller with lighting
- Elitech MTC-6040Temperature and humidity controller
- Elitech EK-3030Refrigeration temperature controller
- Elitech EK-3020 / EK-3021Refrigeration temperature controller
- Elitech ECB-1000PLUS / ECB-1000PLUS CloudCold room control board
- Elitech ECB-LS230 (ECB-LS2xx split control box)Cold room control box
- Elitech LS-200 split control boxCold room control box
- Elitech STC-1000Pro TH / STC-1000WiFi THPlug-in temperature and humidity controller