Elitech MTC-6040

Dual-display controller for chillers and display cases that runs the compressor and fans on temperature and a third relay for lights, humidity or alarm.

What it is: Temperature and humidity controller

Key combo: Hold Set 3 s for the user settings. Press up + Set together for the T1–T15 administrator list.

Elitech MTC-6040 error codes

CodeMeaningLikely causeHow to reset
E1Temperature probe faultProbe open or shortedClears once the probe reads.
E2Humidity sensor faultSensor open or shortedClears once the sensor reads.
HtHigh temperature alarm (alternates with reading)Above SET + HY + EH for longer than T4Alarm-mute key silences the buzzer; the code and alarm relay stay until cleared.
LtLow temperature alarmBelow SET − EL for longer than T4As Ht.
HrHigh humidity alarmAbove T5 for longer than T7As Ht.
LrLow humidity alarmBelow T6 for longer than T7As Ht.

How to enter service / parameter mode

  1. User settings: hold Set more than 3 s. The lower display shows SEt; adjust with up/down and press OK to move on through Hy, ot, oh, EH, EL.
  2. Administrator list: press up and Set together. The lower display shows T1, T2…; the upper shows the value.

Parameter list

CodeWhat it doesRangeDefault / typical
SEtCut-out temperature2 to 20 °C5
HyHysteresis (cut-in = SEt + Hy)0.1 to 15.0 °C2
otTemperature offset−10.0 to 10.0 °C0.0
ohHumidity offset−10 to 10 %RH0
EHHigh alarm, above SEt + Hy0 to 25 °C3
ELLow alarm, below SEt0 to 25 °C3
T1Fan start delay0 to 240 s60
T2Fan stop delay0 to 240 s60
T3Alarm hold-off after power-up0 to 60 h10
T4Temperature alarm delay0 to 60 min10
T5High humidity alarmT6 to 99 %RH75
T6Low humidity alarm0 to T5 %RH10
T7Humidity alarm delay0 to 200 min10
T8Compressor restart delay0 to 15 min3
T9Door alarm delay0 to 15 min5
T10Humidity set point10 to 99 %RH60
T11Humidity hysteresis1 to 50 %RH15
T12Humidity mode0 off, 1 humidify, 2 dehumidify0
T13Third relay0 unused, 1 lights, 2 humidity, 3 alarm0
T14Fan mode (table values)0 with compressor, on when door opens; 1 with compressor, 3 min stop on door open; 2 continuous, 3 min stop on door open; 3 continuous, on when door opens0
T15Power key enabled0 no, 1 yes1

How to change and save a setting

  1. Adjust with up/down and press OK to save and move to the next item.
  2. After the last item OK returns to the first. No key for 30 s saves and exits.

Other useful key presses

TaskHow
Switch on/offHold the power key 3 s (T15 = 1)
Mute buzzerPress the alarm-mute key

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.