Elitech MTC-6040
Dual-display controller for chillers and display cases that runs the compressor and fans on temperature and a third relay for lights, humidity or alarm.
What it is: Temperature and humidity controller
Key combo: Hold Set 3 s for the user settings. Press up + Set together for the T1–T15 administrator list.
Elitech MTC-6040 error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| E1 | Temperature probe fault | Probe open or shorted | Clears once the probe reads. |
| E2 | Humidity sensor fault | Sensor open or shorted | Clears once the sensor reads. |
| Ht | High temperature alarm (alternates with reading) | Above SET + HY + EH for longer than T4 | Alarm-mute key silences the buzzer; the code and alarm relay stay until cleared. |
| Lt | Low temperature alarm | Below SET − EL for longer than T4 | As Ht. |
| Hr | High humidity alarm | Above T5 for longer than T7 | As Ht. |
| Lr | Low humidity alarm | Below T6 for longer than T7 | As Ht. |
How to enter service / parameter mode
- User settings: hold Set more than 3 s. The lower display shows SEt; adjust with up/down and press OK to move on through Hy, ot, oh, EH, EL.
- Administrator list: press up and Set together. The lower display shows T1, T2…; the upper shows the value.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| SEt | Cut-out temperature | 2 to 20 °C | 5 |
| Hy | Hysteresis (cut-in = SEt + Hy) | 0.1 to 15.0 °C | 2 |
| ot | Temperature offset | −10.0 to 10.0 °C | 0.0 |
| oh | Humidity offset | −10 to 10 %RH | 0 |
| EH | High alarm, above SEt + Hy | 0 to 25 °C | 3 |
| EL | Low alarm, below SEt | 0 to 25 °C | 3 |
| T1 | Fan start delay | 0 to 240 s | 60 |
| T2 | Fan stop delay | 0 to 240 s | 60 |
| T3 | Alarm hold-off after power-up | 0 to 60 h | 10 |
| T4 | Temperature alarm delay | 0 to 60 min | 10 |
| T5 | High humidity alarm | T6 to 99 %RH | 75 |
| T6 | Low humidity alarm | 0 to T5 %RH | 10 |
| T7 | Humidity alarm delay | 0 to 200 min | 10 |
| T8 | Compressor restart delay | 0 to 15 min | 3 |
| T9 | Door alarm delay | 0 to 15 min | 5 |
| T10 | Humidity set point | 10 to 99 %RH | 60 |
| T11 | Humidity hysteresis | 1 to 50 %RH | 15 |
| T12 | Humidity mode | 0 off, 1 humidify, 2 dehumidify | 0 |
| T13 | Third relay | 0 unused, 1 lights, 2 humidity, 3 alarm | 0 |
| T14 | Fan mode (table values) | 0 with compressor, on when door opens; 1 with compressor, 3 min stop on door open; 2 continuous, 3 min stop on door open; 3 continuous, on when door opens | 0 |
| T15 | Power key enabled | 0 no, 1 yes | 1 |
How to change and save a setting
- Adjust with up/down and press OK to save and move to the next item.
- After the last item OK returns to the first. No key for 30 s saves and exits.
Other useful key presses
| Task | How |
|---|---|
| Switch on/off | Hold the power key 3 s (T15 = 1) |
| Mute buzzer | Press the alarm-mute key |
Notes
- The manual's written fan-mode list does not match its T14 table; the table values are given here. Check the fan behaviour on the unit after setting T14.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Elitech MTC-6040 operating instructions. Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Elitech or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Elitech pages
- Elitech ECS-180, ECS-180neo and ECS-2280neoRefrigeration controller
- Elitech STC-1000, STC-1000HX and STC-1000XHeat/cool thermostat
- Elitech STC-8000HX and STC-8080HXCooling thermostat
- Elitech STC-200+Cool/heat/alarm thermostat
- Elitech ECS-02CXRefrigeration controller
- Elitech ECS-06CXRefrigeration controller
- Elitech ECS-16Beverage cooler controller
- Elitech ECS-961neoRefrigeration controller
- Elitech ETC-902Heat/cool controller
- Elitech EK-3010 and EK-3010LCool room / heating controller
- Elitech EK-3030ECool room controller
- Elitech ECS-974neo and ETC-974ARefrigeration controller
- Elitech E-1000Heat/cool controller with lighting
- Elitech EK-3030Refrigeration temperature controller
- Elitech EK-3020 / EK-3021Refrigeration temperature controller
- Elitech ECB-1000PLUS / ECB-1000PLUS CloudCold room control board
- Elitech ECB-LS230 (ECB-LS2xx split control box)Cold room control box
- Elitech LS-200 split control boxCold room control box
- Elitech STC-1000Pro TH / STC-1000WiFi THPlug-in temperature and humidity controller