Elitech EK-3030E

Three-relay (compressor, defrost, fan) cool room controller with On/Off temperatures, room and defrost probes, two digital inputs and RS-485 (Modbus RTU).

What it is: Cool room controller

Key combo: Tap lock/OK 1 s to unlock. Hold lock/OK 5 s for the F menu.

Elitech EK-3030E error codes

CodeMeaningLikely causeHow to reset
E1Room probe faultProbe open or shortedCompressor stops 30 min, runs 15 min until fixed.
E2Defrost probe fault (alternates with the reading)Probe open or shortedDefrost runs on interval and time only. Clears once the probe reads.
E1 + E2Both probes failedBoth open or shortedAs E1.
HAHigh temperature alarmRoom at or above On Temp + F11 for longer than F12 (after the F10 power-up hold-off)Clears below On Temp + F11.
LALow temperature alarmRoom at or below Off Temp − F11 for longer than F12Clears above Off Temp − F11.
EAExternal alarm (digital input = 4)Input active for longer than A1Stops as soon as the input clears. Outputs follow A2.
CAEmergency alarm or pressure switch (input = 3 or 2)Input active (for longer than A3 for emergency)Emergency: outputs follow A4, clears with the input. Pressure switch: all relays off, auto-resets up to A8 times, then needs a power-cycle.
dorDoor open too long (input = 1)Door switch active for longer than A5Clears when the door closes. Fan/compressor follow A6 and A7.
ErrSettings did not saveMemory write errorReturns to normal after 5 s.

How to enter service / parameter mode

  1. Press lock/OK 1 s to unlock (keypad relocks after 30 s idle).
  2. Temp On / Temp Off: tap the key, adjust with up/down, press lock/OK.
  3. System menu: hold lock/OK more than 5 s until F1 shows.
  4. Hidden list: inside the system menu hold the defrost key 5 s and enter the access code from the manual.

Parameter list

CodeWhat it doesRangeDefault / typical
Temp OnCut-in (cooling)Temp Off to 85 °C10.0 °C
Temp OffCut-out (cooling)−40 °C to Temp On−10.0 °C
F1Defrost time1 to 120 min30
F2Defrost interval0 to 120 h6
F3Interval counts0 controller on time, 1 compressor run time, 2 external timer via digital input1
F4Drip time0 to 120 min3
F5Defrost type0 electric, 1 hot gas, 2 air (fan)0
F6Defrost end temperature−40 to 50 °C10
F7Fan mode−180 to −1 s fan leads compressor; 0 with compressor; c always on; d on but off in defrost and drip; 1 to 300 s fan lags compressor0
F8Fan delay after drip0 to 300 s30
F9Compressor restart delay0 to 10 min0
F10Alarm hold-off after power-up0 to 24 h2
F11Alarm band0 to 50.0 °C5.0
F12Alarm delay0 to 120 min10
H15 / H16Digital input 1 / 20 off, 1 door, 2 pressure switch, 3 emergency alarm, 4 external alarm, 5 heating mode, 6 defrost start. Positive = N/O, negative = N/C0
H17Network address (0 = off)0 to 1281
A1External alarm delay0 to 240 s60
A2Outputs on external alarm0 no change, 1 compressor off, 2 all off0
A3Emergency alarm delay0 to 240 s0
A4Outputs on emergency alarm0 no change, 1 compressor off, 2 all off0
A5Door alarm delay0 to 240 s60
A6Door open action0 none, 1 fan off, 2 compressor off, 3 both off3
A7Fan stop time with door openON never stops, OFF stays off until door closes, 1 to 240 s40
A8Pressure switch auto-resets (0 = manual only)0 to 52

How to change and save a setting

  1. Step with up/down, tap lock/OK to show the value.
  2. Adjust with up/down and tap lock/OK to store.
  3. Hold lock/OK 3 s, or wait 30 s, to save and exit.

Other useful key presses

TaskHow
Manual defrostHold the defrost key 3 s (defrost probe below F6). Hold again 3 s to stop
Show defrost probeHold down
Save installer presetLocked: hold Temp On 10 s, COP shows, press lock/OK
Load installer presetLocked: hold Temp Off 10 s, DON shows, press lock/OK

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech EK-3030E user manual (V2.1). Always check the manual for your exact model and software version.

ServiceModes is not affiliated with Elitech or any other manufacturer. Written in our own words from the manufacturer's documentation.