Elitech STC-200+
Basic one-relay thermostat whose single output can be set to cool, heat or act as an alarm contact.
What it is: Cool/heat/alarm thermostat
Key combo: Set + up for 5 s opens the administrator (F0–F5) menu. Set alone for 5 s changes only the set point.
Elitech STC-200+ error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| E1 | Probe open circuit | Probe broken or unplugged | Flashing display and buzzer. In cooling mode the compressor runs 15 min, stops 15 min until fixed. |
| E2 | Probe short circuit | Probe or lead shorted | As E1. |
| HH | Above +99 °C | Reading over the top of the range | Clears when the reading falls. |
| LL | Below −40 °C | Reading under the bottom of the range | Clears when the reading rises. |
How to enter service / parameter mode
- Hold Set and up together for 5 seconds. The set light comes on and F0 shows.
- Step with up or down. Press Set to open a code.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| F0 | Differential | 1 to 16 °C | 3 °C |
| F1 | Compressor delay | 0 to 8 min | 3 min |
| F2 | Lowest allowed set point | −50 °C to set point | −30 °C |
| F3 | Highest allowed set point | Set point to 99 °C | 10 °C |
| F4 | Output mode | 1 refrigeration, 2 heating, 3 alarm | 1 |
| F5 | Probe offset | −5 to +5 °C | 0 |
How to change and save a setting
- Change the value with up or down and press Set to go back to the code list.
- Hold Set 5 seconds, or wait 30 seconds, to save and leave.
Other useful key presses
| Task | How |
|---|---|
| Change set point | Hold Set 5 s, then up or down |
| See set point / differential | Tap up / tap down |
| Turn on or off | Hold the on/off key 3 s |
Notes
- Alarm mode (F4 = 3): the relay closes when the temperature goes above set point + differential or below set point − differential.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Elitech STC-200 instruction (V2.0). Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Elitech or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Elitech pages
- Elitech ECS-180, ECS-180neo and ECS-2280neoRefrigeration controller
- Elitech STC-1000, STC-1000HX and STC-1000XHeat/cool thermostat
- Elitech STC-8000HX and STC-8080HXCooling thermostat
- Elitech ECS-02CXRefrigeration controller
- Elitech ECS-06CXRefrigeration controller
- Elitech ECS-16Beverage cooler controller
- Elitech ECS-961neoRefrigeration controller
- Elitech ETC-902Heat/cool controller
- Elitech EK-3010 and EK-3010LCool room / heating controller
- Elitech EK-3030ECool room controller
- Elitech ECS-974neo and ETC-974ARefrigeration controller
- Elitech E-1000Heat/cool controller with lighting
- Elitech MTC-6040Temperature and humidity controller
- Elitech EK-3030Refrigeration temperature controller
- Elitech EK-3020 / EK-3021Refrigeration temperature controller
- Elitech ECB-1000PLUS / ECB-1000PLUS CloudCold room control board
- Elitech ECB-LS230 (ECB-LS2xx split control box)Cold room control box
- Elitech LS-200 split control boxCold room control box
- Elitech STC-1000Pro TH / STC-1000WiFi THPlug-in temperature and humidity controller