Elitech STC-8000HX and STC-8080HX

Two-digit, whole-degree cooling controller that runs the compressor between an upper (cut-in) and lower (cut-out) temperature, with a high/low alarm.

What it is: Cooling thermostat. The STC-8080HX adds a defrost relay and the F7/F8 defrost settings. Both are the -02 versions.

Key combo: Hold Set for 3 s to open the F-menu.

Elitech STC-8000HX and STC-8080HX error codes

CodeMeaningLikely causeHow to reset
E1Memory (stored settings) faultError found in the saved data at power-upController will not run. Press Set to load factory values, then re-enter your settings.
E2Probe faultProbe open or shortedBuzzer sounds. Compressor runs 15 min, stops 30 min until fixed. Clears once the probe reads.
HHAbove display rangeMeasured temperature between 99 and 120 °CClears when the reading drops.
(flashing reading)High or low temperature alarmAbove F1 + F5 or below F2 − F5 for longer than F6Buzzer and flashing display. Any key mutes the buzzer. Clears when back in range.

How to enter service / parameter mode

  1. Hold Set for 3 seconds. The set (spanner) light comes on and the last code you edited shows.
  2. Step through the codes with up or down. Press Set to see a value.

Parameter list

CodeWhat it doesRangeDefault / typical
F1Cut-in (upper) temperatureF2 to 50 °C−10 °C
F2Cut-out (lower) temperature−40 °C to F1−20 °C
F3Probe offset−5 to +5 °C0
F4Compressor restart delay0 to 9 min3
F5Alarm band beyond F1/F2 (0 = no alarm)0 to 50 °C15
F6Alarm delay0 to 99 min20
F7Defrost interval, 8080HX (0 = no timed defrost)0 to 99 h8
F8Defrost time, 8080HX (0 = no timed defrost)0 to 99 min20

How to change and save a setting

  1. Hold Set and press up or down to change the value (hold both to run fast).
  2. Press Rst, or leave it 30 seconds, to save and exit.

Other useful key presses

TaskHow
See cut-in / cut-outTap up / tap down
See restart delay (8000HX) or defrost interval (8080HX)Tap Set
See alarm band (8000HX) or defrost time (8080HX)Tap Rst
Manual defrost on / off (8080HX)Hold up 3 s to start; hold down 3 s to stop

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech STC-8000HX-02 and STC-8080HX-02 user manuals (V1.0). Always check the manual for your exact model and software version.