Elitech EK-3010 and EK-3010L
Six-key touch controller with one relay that switches on and off at two separate temperatures (On Temp and Off Temp), in cooling or heating mode.
What it is: Cool room / heating controller. Both models use the same On Temp / Off Temp keys and F9–F14 / H1–H6 settings.
Key combo: Tap the lock/OK key 1 s to unlock. Hold lock/OK 5 s for the system (F) menu.
Elitech EK-3010 and EK-3010L error codes
| Code | Meaning | Likely cause | How to reset |
|---|---|---|---|
| E1 | Cabinet probe fault | Probe open or shorted | Compressor stops for H1 (30 min) then runs H2 (15 min) until the probe reads again. Buzzer sounds. |
| HA | High temperature alarm (alternates with the reading) | Refrigeration: above On Temp + F11 for longer than F12. Heating: above Off Temp + F11 | Clears once back inside the band. Any key mutes the buzzer. |
| LA | Low temperature alarm (alternates with the reading) | Refrigeration: below Off Temp − F11 for longer than F12. Heating: below On Temp − F11 | As HA. |
| Err | Settings did not save | Memory write error | Returns to normal after 5 s. Power-cycle and set again. |
| rES / COP / don | Reset prompts | Factory reset, save installer preset, load installer preset | Press the lock/OK key within 3 s to confirm; YES shows. |
How to enter service / parameter mode
- The keypad locks itself after 30 s idle (padlock lit). Press the lock/OK key for 1 second to unlock.
- On Temp and Off Temp: tap the matching key, adjust with up/down, press lock/OK to save.
- System menu: hold lock/OK for more than 5 seconds. The first F code shows.
- Hidden H menu (EK-3010): inside the system menu hold the defrost key 5 s and enter the access code given in the manual.
Parameter list
| Code | What it does | Range | Default / typical |
|---|---|---|---|
| On Temp | Temperature where the output switches on | Cooling: Off Temp to 85 °C. Heating: −40 °C to Off Temp | Cooling 10.0 °C |
| Off Temp | Temperature where the output switches off | Cooling: −40 °C to On Temp. Heating: On Temp to 85 °C | Cooling −10.0 °C |
| F9 | Compressor restart delay | 0 to 10 min | 0 |
| F10 | Alarm hold-off after power-up | 0 to 24.0 h | 2.0 h |
| F11 | Alarm band | 0 to 50.0 °C | 5.0 |
| F12 | Alarm delay | 0 to 120 min | 10 |
| F13 | Probe offset | −10.0 to 10.0 °C | 0.0 |
| F14 | Mode | 0 cooling, 1 heating | 0 |
| H1 | Off time with probe fault | 1 to 60 min | 30 |
| H2 | On time with probe fault | 0 to 60 min | 15 |
| H3 | High alarm (absolute mode) | H4 to 85 °C | 20.0 |
| H4 | Low alarm (absolute mode) | −40 °C to H3 | −20.0 |
| H5 | Alarm mode | 0 absolute (H3/H4), 1 relative to On/Off Temp ± F11 | 1 |
| H6 | Buzzer on alarm | 0 no, 1 yes | 1 |
How to change and save a setting
- Step to the code with up/down and tap lock/OK to show the value.
- Adjust with up/down (hold to run fast), tap lock/OK to store.
- Hold lock/OK 5 s, or wait 30 s, to save and exit.
Other useful key presses
| Task | How |
|---|---|
| Factory reset | Locked: hold up 10 s, rES shows; press lock/OK within 3 s |
| Save installer preset | Locked: hold On Temp 10 s, COP shows; press lock/OK |
| Load installer preset | Locked: hold Off Temp 10 s, don shows; press lock/OK. Power-cycle afterwards |
| Mute buzzer | Any key |
Notes
- Power-cycle the controller after any reset or preset load.
- If no installer preset was ever saved, loading it gives factory defaults.
For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.
Based on: Elitech EK-3010 and EK-3010L temperature controller user manuals. Always check the manual for your exact model and software version.
ServiceModes is not affiliated with Elitech or any other manufacturer. Written in our own words from the manufacturer's documentation.
More Elitech pages
- Elitech ECS-180, ECS-180neo and ECS-2280neoRefrigeration controller
- Elitech STC-1000, STC-1000HX and STC-1000XHeat/cool thermostat
- Elitech STC-8000HX and STC-8080HXCooling thermostat
- Elitech STC-200+Cool/heat/alarm thermostat
- Elitech ECS-02CXRefrigeration controller
- Elitech ECS-06CXRefrigeration controller
- Elitech ECS-16Beverage cooler controller
- Elitech ECS-961neoRefrigeration controller
- Elitech ETC-902Heat/cool controller
- Elitech EK-3030ECool room controller
- Elitech ECS-974neo and ETC-974ARefrigeration controller
- Elitech E-1000Heat/cool controller with lighting
- Elitech MTC-6040Temperature and humidity controller
- Elitech EK-3030Refrigeration temperature controller
- Elitech EK-3020 / EK-3021Refrigeration temperature controller
- Elitech ECB-1000PLUS / ECB-1000PLUS CloudCold room control board
- Elitech ECB-LS230 (ECB-LS2xx split control box)Cold room control box
- Elitech LS-200 split control boxCold room control box
- Elitech STC-1000Pro TH / STC-1000WiFi THPlug-in temperature and humidity controller