Elitech EK-3010 and EK-3010L

Six-key touch controller with one relay that switches on and off at two separate temperatures (On Temp and Off Temp), in cooling or heating mode.

What it is: Cool room / heating controller. Both models use the same On Temp / Off Temp keys and F9–F14 / H1–H6 settings.

Key combo: Tap the lock/OK key 1 s to unlock. Hold lock/OK 5 s for the system (F) menu.

Elitech EK-3010 and EK-3010L error codes

CodeMeaningLikely causeHow to reset
E1Cabinet probe faultProbe open or shortedCompressor stops for H1 (30 min) then runs H2 (15 min) until the probe reads again. Buzzer sounds.
HAHigh temperature alarm (alternates with the reading)Refrigeration: above On Temp + F11 for longer than F12. Heating: above Off Temp + F11Clears once back inside the band. Any key mutes the buzzer.
LALow temperature alarm (alternates with the reading)Refrigeration: below Off Temp − F11 for longer than F12. Heating: below On Temp − F11As HA.
ErrSettings did not saveMemory write errorReturns to normal after 5 s. Power-cycle and set again.
rES / COP / donReset promptsFactory reset, save installer preset, load installer presetPress the lock/OK key within 3 s to confirm; YES shows.

How to enter service / parameter mode

  1. The keypad locks itself after 30 s idle (padlock lit). Press the lock/OK key for 1 second to unlock.
  2. On Temp and Off Temp: tap the matching key, adjust with up/down, press lock/OK to save.
  3. System menu: hold lock/OK for more than 5 seconds. The first F code shows.
  4. Hidden H menu (EK-3010): inside the system menu hold the defrost key 5 s and enter the access code given in the manual.

Parameter list

CodeWhat it doesRangeDefault / typical
On TempTemperature where the output switches onCooling: Off Temp to 85 °C. Heating: −40 °C to Off TempCooling 10.0 °C
Off TempTemperature where the output switches offCooling: −40 °C to On Temp. Heating: On Temp to 85 °CCooling −10.0 °C
F9Compressor restart delay0 to 10 min0
F10Alarm hold-off after power-up0 to 24.0 h2.0 h
F11Alarm band0 to 50.0 °C5.0
F12Alarm delay0 to 120 min10
F13Probe offset−10.0 to 10.0 °C0.0
F14Mode0 cooling, 1 heating0
H1Off time with probe fault1 to 60 min30
H2On time with probe fault0 to 60 min15
H3High alarm (absolute mode)H4 to 85 °C20.0
H4Low alarm (absolute mode)−40 °C to H3−20.0
H5Alarm mode0 absolute (H3/H4), 1 relative to On/Off Temp ± F111
H6Buzzer on alarm0 no, 1 yes1

How to change and save a setting

  1. Step to the code with up/down and tap lock/OK to show the value.
  2. Adjust with up/down (hold to run fast), tap lock/OK to store.
  3. Hold lock/OK 5 s, or wait 30 s, to save and exit.

Other useful key presses

TaskHow
Factory resetLocked: hold up 10 s, rES shows; press lock/OK within 3 s
Save installer presetLocked: hold On Temp 10 s, COP shows; press lock/OK
Load installer presetLocked: hold Off Temp 10 s, don shows; press lock/OK. Power-cycle afterwards
Mute buzzerAny key

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech EK-3010 and EK-3010L temperature controller user manuals. Always check the manual for your exact model and software version.