Elitech ECS-961neo

One-probe, one-relay (17 A) cabinet controller with off-cycle defrost timing, cooling or heating mode, and an access-code administrator menu.

What it is: Refrigeration controller

Key combo: Tap Set for the set point. Hold Set 5 s for PA1 (administrator access code).

Elitech ECS-961neo error codes

CodeMeaningLikely causeHow to reset
E1Probe faultRoom probe open or shortedCompressor follows Ont/OFt: Ont 0 = off, OFt 0 = on, both above 0 = cycling. Clears once the probe reads.
ErCopy card failedCard not seated or faultyReseat and repeat.
EPCopy card data does not matchCard from another modelUse the right card or upload to it first.
LOCSet point lockedLOC = yChange LOC to n in the administrator menu.
rStUser values restoredUp + down held 10 sInformation only.

How to enter service / parameter mode

  1. Hold Set for 5 seconds: PA1 shows. If PA1 is set to 0 the administrator list opens directly.
  2. Otherwise press Set (00 shows), enter the administrator access code with up/down and press Set. If the code is right the list opens at diF; if wrong, the controller drops back to normal.

Parameter list

CodeWhat it doesRangeDefault / typical
SEtSet pointLSE to HSE4.0 °C
diFDifferential0.1 to 30.0 °C2.0
HSEHighest set pointSEt to 99 °C90.0
LSELowest set point−50 °C to SEt−50.0
OntOn time with probe fault0 to 250 min0
OFtOff time with probe fault0 to 250 min1
dOFCompressor restart delay0 to 250 min0
OdOOutput delay at power-up0 to 250 min0
ditDefrost interval1 to 250 h6
dCtInterval counts0 compressor run time, 1 clock time, 2 compressor off time1
dOHDelay before first defrost1 to 59 min1
dEtDefrost time (0 = no defrost)0 to 250 min30
dPODefrost at power-upn / yn
LOCLock set pointn / yn
PA1Administrator access code (set your own; 0 = no code)0 to 250see manual
ndtShow decimal pointn / yy
CA1Probe offset−12.0 to 12.0 °C0
ddLDisplay in defrost0 live, 1 frozen until back at set point, 2 dEF until back at set point1
HCMode0 cooling, 1 heating0

How to change and save a setting

  1. Pick a code with up or down and press Set.
  2. Adjust with up or down, then press Set to go back to the list.
  3. Press the defrost key, or wait 30 s, to save and exit.

Other useful key presses

TaskHow
Manual defrost on/offHold the defrost key 3 s
Restore user valuesHold up + down 10 s until rSt
Copy card upload / downloadCard in, hold up (uP) or down (do), remove after 5 s

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech ECS-961neo temperature controller manual. Always check the manual for your exact model and software version.