Elitech ETC-902

Small one-relay (8 A) controller that heats or cools around a set point and accepts either an NTC or PTC probe, with settings grouped into folders.

What it is: Heat/cool controller

Key combo: Hold SET 5 s for the parameter folders (CP, diS, CnF, FPr). FNC backs out.

Elitech ETC-902 error codes

CodeMeaningLikely causeHow to reset
E1Probe faultProbe type does not match H00, wiring fault, or failed probeCompressor runs on the Ont / OFt cycle. Check H00 first, then measure the probe resistance.
(alarm icon)Out of range or probe faultTemperature out of range, or probe faultAny key mutes the buzzer (buzzer is a factory option).
dLY / DLnCopy card load passed / failedCard inserted with power off, then power onDLn: reseat the card and try again.

How to enter service / parameter mode

  1. Hold SET for 5 seconds. CP (first folder) shows. If a user access code is set in PA1, PAI shows first: press SET and enter it with the arrow keys.
  2. Use the arrows to pick a folder (CP, diS, CnF, FPr) and press SET to open it.

Parameter list

CodeWhat it doesRangeDefault / typical
diFDifferential1 to 30 °2
HSEHighest set pointLSE to 9999
LSELowest set point−55 to HSE−55
HCModeH heating, C coolingH
OntOn time with probe fault0 to 250 min0
OFtOff time with probe fault0 to 250 min1
dOnCompressor start delay0 to 250 s0
dOFMinimum off time0 to 250 min0
dbiMinimum time between two starts0 to 250 min0
OdOOutput delay at power-up0 to 250 min0
LOCLock the set pointn / yn
PA1User access code (0 = none)0 to 2500
ndtShow decimalsn / yn
CA1Probe offset−12 to 120
droUnits0 °C, 1 °F0
H00Probe type0 PTC, 1 NTC1
rELFirmware versionRead only—
tAbParameter tableRead only—
UL / dLUpload to / download from copy cardPress SET, y = done—

How to change and save a setting

  1. Step to the code with the arrows and press SET to see its value.
  2. Change it with the arrows and press SET.
  3. Press FNC to go back up to the folder list, and FNC again to return to the temperature display.

Other useful key presses

TaskHow
Change set pointTap SET, adjust with the arrows, press FNC
Mute buzzerAny key

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech 902 operation instructions (V1.0). Always check the manual for your exact model and software version.