Elitech ECS-180, ECS-180neo and ECS-2280neo

Cabinet controller with compressor, defrost (electric or hot gas), fan and light/alarm relays, plus optional evaporator, condenser and door inputs.

What it is: Refrigeration controller. Covers the ECS-180 (the A and B sheets are the same document) and the ECS-180neo, which adds fan temperature limits (F4/F5) and a °C/°F setting (u1). The ECS-2280neo has the same list as the neo plus RS-485 addresses (Adr, un1), an optional UPS input and a 100–240 V supply. Two hardware builds exist: a 30 A compressor relay version without light relay or backup supply, and a 5 A version with light/alarm relay and 7–13.5 V DC standby input.

Key combo: Hold Set for 3 s for the user menu. The full list sits behind the Po access code.

Elitech ECS-180, ECS-180neo and ECS-2280neo error codes

CodeMeaningLikely causeHow to reset
E1Cabinet probe faultProbe open or shortedAutomatic once the probe reads again. Compressor then follows A1: off, or cycling on A3 run / A2 stop minutes.
E2Evaporator probe faultProbe open or shorted (only with d1 = 1)Automatic once the probe reads. Defrost ends on time (d6).
E3Condenser probe faultProbe open or shorted (only with cd1 = 1)Automatic once the probe reads.
cHCondenser too hotCondenser above cd2. Display only, outputs keep runningClears when condenser drops below cd2 minus cd3. Clean the condenser and check the fan.
rHCabinet high temperatureAbove A6 (A11 = 0) or set point + A9 (A11 = 1) for longer than A7 (A8 after power-up)Clears by itself once the cause is fixed.
rLCabinet low temperatureBelow A5 (A11 = 0) or set point − A10 (A11 = 1) for longer than A7Clears by itself once the cause is fixed.
ErCopy card failed (neo)Card not seated or faultyReseat and repeat.
EPCopy card data does not match (neo)Card from another modelUse the right card.

How to enter service / parameter mode

  1. Hold Set for 3 seconds. St (set point) shows: press Set to view it and the light or rotate key to change it.
  2. To reach the full list, step to Po, press Set and enter the administrator access code from the manual with the light and rotate keys, then press Set.
  3. If the code is right, every parameter (C1 … cd3) becomes visible. If not, only St and Po show. The code has to be entered again each time you open the menu.

Parameter list

CodeWhat it doesRangeDefault / typical
StSet pointC5 to C64 °C
C1Hysteresis0.5 to 9.0 °C4.0 °C
C2Minimum compressor off time between starts0 to 60 min5
C3Compressor delay at first power-up0 to 90 min5
C4Cabinet probe offset−10 to +10 °C0
C5Lowest allowed set point−50 °C to St−2 °C
C6Highest allowed set pointSt to 85 °C22 °C
C7Maximum standby once inside the band (0 = off)0 to 90 min9
C8Minimum compressor run time (0 = off)0 to 90 min0
d1Evaporator probe fitted0 no, 1 yes1
d2Evaporator probe offset−10 to +10 °C0
d3Defrost interval counts0 compressor run time, 1 clock time1
d4Defrost interval (0 = no defrost)0 to 90 h2
d5Display during defrost0 cabinet temp, 1 dEF until delay ends, 2 dEF through drip, 3 frozen reading2
d6Maximum defrost time1 to 90 min25
d7Defrost end temperature0 to 50 °C12 °C
d8Drip time (0 = none)0 to 60 min2
d9Display hold after defrost0 to 90 min10
d10Delay before defrost output starts0 to 30 min10
d11Defrost type0 electric, 1 hot gas0
F1Fan mode0 with compressor, 1 on but off in defrost, 2 off in defrost and drip, 3 off until F3 after defrost, 4 (neo only) by evaporator temperature, off in defrost3
F2Fan delay at power-up0 to 60 min4
F3Fan delay after defrost0 to 60 min2
F4Fan lowest working temperature (neo only)−50 °C to F5−12 °C
F5Fan highest working temperature (neo only)F4 to 85 °C−5 °C
A1Compressor action on cabinet probe fault0 off, 1 timed cycling1
A2Off time when cycling on probe fault1 to 60 min5
A3Run time when cycling on probe fault1 to 60 min30
A4Buzzer0 off, 1 on1
A5Low alarm (absolute)−50 °C to A6−10 °C
A6High alarm (absolute)A5 to 85 °C24 °C
A7Alarm delay0 to 60 min20
A8Alarm delay after power-up0 to 60 min40
A9High alarm offset (relative mode)1 to 30 °C10 °C
A10Low alarm offset (relative mode)1 to 30 °C5 °C
A11Alarm mode0 absolute (A5/A6), 1 relative to set point0
A12Light/alarm relay use0 light, 1 alarm0
do1Door input0 off, 1 fans stop, 2 light on, 3 fans stop + light on, 4 used as remote defrost start0
do2Buzzer on door open0 no, 1 yes0
cd1Condenser probe fitted0 no, 1 yes1 (neo: 0)
cd2Condenser alarm temperature30 to 90 °C55 °C
cd3Condenser alarm reset band1 to 15 °C5 °C
u1Units (neo only)00 °F, 01 °C01
AdrController network address (2280neo)00 to 12701
un1Unit network address (2280neo)00 to 12701

How to change and save a setting

  1. Pick the code with the light (up) or rotate (down) key and press Set.
  2. Change the value with the same keys and press Set to go back to the list.
  3. Press the defrost (Rst) key, or wait 30 seconds, to save and exit.

Other useful key presses

TaskHow
Show evaporator temperatureTap the defrost key (probe enabled)
Show condenser temperatureTap the rotate key (probe enabled)
Manual defrost / step the cycleHold the defrost key 3 s
Factory resetHold the rotate key 10 s: H0 shows. Pick H1 to H6 (°C presets) or H7 (°F preset) and press defrost. dr confirms. H0 cancels.

Notes

For licensed technicians only. This equipment can involve mains voltage, high-voltage microwave circuits, gas and refrigerant. Isolate power (and gas) before opening panels, follow the manufacturer's manual and your local licensing rules (for example ARC refrigerant handling and electrical or gas licences). Wrong settings can spoil food or damage equipment. Check every value on the unit in front of you before changing it.

Based on: Elitech ECS-180 temperature controller user manual (A/B sheets) ECS-180neo and ECS-2280neo user manuals. Always check the manual for your exact model and software version.